Y47 - SSW ventilation Flashcards

1
Q

What are the auto starts for the ventilation fans?

A

1Y47-C004A/B pump start or > 100 deg F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are the auto starts for 2Y47-C001A?

A

> 100 deg F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

How do you stop a fan after it auto-starts?

A

Take the handswitch to stop. (no auto stop)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How is a fan stopped with initiation signal still in?

A

Open the breaker

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

what’s the purpose of the room heater?

A

Auto start to heat room @ 50 deg F +- 10 deg F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What’s the purpose of SSW ventilation?

A

to provide air circulation in the SSW pumphouse, it also provides heated air when room temp get to low

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What’s the power supply to 1Y47-C001A

A

15B51

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What’s the power supply to 1Y47-C001B and 2Y47-C001A

A

16B51

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What are the temp limits of the SSW pumphouses?

A

Outside temp < 94 deg F maixmum temp of 104 deg F

Outside temp is > 94 deg F limit is outside temp plus 10 deg F up until 111 deg F, which is the maximum limit?

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

How do dampers align after a start signal?

A

Exhaust F001 full open

Intake F002 > 45 deg F full open < 45 deg F intermediate

Recirc F003 > 45 deg F full closed < 45 deg F full open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly