When is manual control used?
< 100 rpm
When will the controller auto swap from speed auto to manual? (going down)
< 300 rpm
Speed sensor fail hydraulic servo slave failure
both stop valves not full open
turbine trip
When is it preferred to swap from speed auto to feed auto?
2100 rpm
When will it auto swap from feed auto back to speed auto?
Speed signal exceeds the HSS limit (High speed stop)
speed below LSS limit
Signal “bad quality”
signal processing circuit fail (slave module)
When is emergency manual activated?
when digital control senses Hydraulic servo slave module is not in communication with the multi-functional processor
What is a risk of emergency manual mode?
OVERSPEED because there is no feedback to INFI-90
What’s the power supply for the RFPT speed control?
1Y99
Where does the RFPT turbine exhaust to?
HP condenser
What power levels is Start-up level control used for?
0-20%
What Rx power can you go to with the loss of HP feedwater heater string?
95%
What should vacuum be maintained at when the turbine is in operation? (vacuum in the RFPT lube oil tank)
> .5” wc or write a CR
How many low pressure steam poppets are there?
7
How many high pressure steam poppets are there?
1
Which poppets are used during start up? (low or high pressure poppets)
High pressure
At what reactor pressure, should you put in a feed pump?
400 psig