P41 - SSW Flashcards
What are the types of auto starts for SSW A/B, and what is cooled with each type of start?
Component start - cools that component
LOCA - cools all divisional components
Manual initiation - cools all divisional components
LOP - switchgear room
What powers the logic to each SSW pump?
A - 11DA
B - 11DB
C - 11DC
What are the SSW A/B pump and fan trips?
Will pumps re-start when power is restored?
MPD and LOP
YES
How does SSW C auto start regardless of the signal?
Return valve opens, THEN
10 seconds later - Pump starts
If H22-P152 is placed in ON position what features are lost?
Control room indication
hand switches
Auto start features are disabled for Div 1
What will cause a component start for SSW A?
RHR A/LPCS breaker closed
E51-F045 not full closed (RCIC steam supply)
Diesel > 200 rpm
What will cause a component start for SSW B?
RHR B/C breaker closed
Diesel > 200 rpm
How does the make-up valve F113 respond to a LOCA?
closed and cannot be re-opened until signal is clear
When does the makeup valve F113 open/close?
Open 17”
Close 33.5”
When does the HI/LO Alarm come in for the head tank
Hi 41”
Low 17”
Can SSW fan be secured with auto initiation signal sealed in?
NO
Where can fans be operated from?
P870, remote shutdown panel, and alternate shutdown panel (P299)
What’s the make-up water for SSW?
PSW (P21 back-up)
How long is SSW available with no make-up water
30 days
How much water is in the SSW basins?
15 million gallons
What do the blowdown valves do on a LOCA signal?
Close and cannot be opened until signal is clear
Where can Div 1 blowdown valve be operated from other than the main control room?
Alternate Shutdown Panel
What’s the purpose of the recirc valve F002A/B?
It’s throttled and de-energized to maintain pump discharge below relief valve setpoint
When will it auto close? (recirc valve)
Auto start and heat exchanger inlet/outlet are full open or if LOCA or CTMT spray signal present
Can it manually be opened with LOCA or CTMT spray signal sealed in? (recirc valve)
NO
When does the discharge valve F001A/B open?
On auto start signal and cannot be closed until the signal is clear
When does the F005 A/B test return auto-open?
on auto start
is it throttleable?
Yes during normal OPS (no auto start)