P11 - CST/CRWST Transfer Flashcards

1
Q

What valves auto close on high flow? and why?

A

P11-F514, 513, F011 (CRWST valves) to supply water to CTMT fire water system.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What flow do the CRWST valves close at? (high flow due to CTMT fire water system)
and when will they reopen?

A

Close @ > 9.9” water column after 5 sec TD

re-open @ < 9.9” water column

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What’s the purpose of CST/CRWST transfer system?

A

Primary source of water of HPCS, RCIC, CRD, seal steam, and CTMT fire protection system. Also transfers water from upper CTMT pool during refueling operations and from cask storage.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is lost if instrument air is lost?

A

Fire water to CTMT (normal supply)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

In the event of a group 6 isolation, what will be lost?

A

Fire water to CTMT

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Where are the RWST pumps operated?

A

Locally

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What are the RWST pump trips?

A

Low suction pressure, MPD

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

How do the valves fail on loss of air?

A

All close except for F505 (condensate transfer pump recirc valve fails open)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What’s the only continuously supplied load from CRWST system?

A

Seal steam

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

When will the standby condensate transfer pump start?

A

< 76 psig (must be manually secured)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What’s the normal suction supply of the condensate transfer pumps?

A

CST

How well did you know this?
1
Not at all
2
3
4
5
Perfectly