Wire Bus Type Flashcards

1
Q

Copper or aluminum wire is used to connect equipment bushings to substation bus because it will flex.

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

? is the conductor of choice for substation equipment connections because of its high resistance to corrosion.

A

AAC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

ACSR and AAC conductors have the same current carrying capacity for the same size wire.

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Reusing bolts on spade terminals may result in a clamping force drop-off of approximately ? after being retightened twice.

A

30%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Bimetallic AL/CU connections require ? bolts equipped with Belleville-type spring washers.

A

stainless steel

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

The antioxidants used when making aluminum-aluminum connections use a natural (petroleum) base to suspend particles of ? , which act as a sacrificial metal.

A

zinc

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Bolted connections are popular for attaching conductors to substation equipment because they permit easy disconnection for maintenance.

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

If silicon bronze bolts are used to bolt a lug to the equipment terminal in a substation, the nuts are torque to ? .

A

40 ft-lb

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

When silicon bronze bolts are used on copper or electrical bronze terminal lugs, ? washers are usually used under both the bolt heads and nuts.

A

silicon bronze

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

When an aluminum conductor is connected to a flat copper or electrical bronze equipment terminal, a(n) ? terminal lug is used.

A

aluminum

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

When connecting aluminum and copper conductors, the aluminum should be on the bottom to absorb the copper salts from the copper conductor.

A

False

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Aluminum bolts should not be reused after they have been torqued.

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Do not wire brush ? terminal contact surfaces.

A

tin or silver plated

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

A connection joining copper to aluminum terminal pad will be bolted with stainless steel or ? hardware.

A

galvanized steel

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Aluminum bolts must be lubricated to attain proper torque values.

A

True

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

A lubricated aluminum alloy nut is torqued to ? on a 1/2-inch bolt

A

25 ft-lb

17
Q

To avoid seizing, it is often recommended that stainless steel bolts be fitted with ? nuts.

A

bronze

18
Q

The table in the text reference recommends a torque setting of ? for 1/2-inch silicon-bronze nuts and bolts.

A

40 ft-lb

19
Q

Duroze or Everdur bolts are typically used for ? connections.

A

copper-to-copper

20
Q

All aluminum-bronze alloy and copper-bronze alloy terminal pads require an antioxidant to be applied to the contact surfaces.

A

False