Superstructure Assembly and Erection Part 2 Flashcards
The winch and stinger can lift loads in certain positions that will overload the boom.
True
Damage to the rotation gear of a digger derrick can be caused by ? .
operating a heavy load with the truck set up on a slope
The lifting capacity of a digger derrick is decreased when ? .
the boom is extended away from the turret
The lifting capacity chart for each digger derrick must be ? .
visible from the boom operator’s position
On a digger derrick, the stinger will not extend if the overload protection is working.
True
The lifting capacity changes with the direction of the boom in relation to the truck, outriggers, and slope of the ground. A typical chart will show a ? rating when operating the boom over the side and at a 5° slope.
60%
The maximum working load for a one-inch double-braided polyester winch rope is ? .
6,000 lbs
The assembly area for substation structures should be planned so that a digger derrick can lift each section in the sequence it will set up.
True
To determine the Working Load Limit (WLL) of rigging components, the ? is divided by the safety factor.
breaking strength
When the nuts are installed, the bolts should be long enough so that at least ? thread(s) is/are seen protruding through the nut.
2
As a substation structure is placed, the nuts are torqued to their required values before all bolts are set in place to prevent it from slipping.
False
A synthetic web sling has a catalog breaking strength of five tons. Using the typical safety factor for synthetic web slings, determine the WLL.
2000 lbs
In order to maintain a safe distance from a section being hoisted, tag lines should be used to control the section.
True
Sling angle is the angle ? .
a sling leg makes with an imaginary horizontal line
When two sling legs are used in a lift and the sling angle is ? , the tension on each sling leg is equal to the weight of the load.
30°