Unit 8: Single Family Dwelling Service Calculations Flashcards

Using NEC® demand factors and load calculation methods to determine the appropriate service size, conductor sizing, and overcurrent protection for single-family dwellings.

1
Q

Fill in the blank:

When determining the initial standard size time-delay fuses for branch-circuit, short circuit and ground-fault protection for a three-phase, continuous-duty, squirrel cage, ac motor, the fuses shall have a rating of ________ of the full-load current rating of the motor. When the value determined does not correspond to a standard ampere rating, the next higher standard rating shall be permitted.

A

175 percent

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Fill in the blank:

A junction box to be installed will contain five (5) size 12 AWG conductors and six (6) size 10 AWG conductors. The junction box is required to have a volume of at LEAST ________.

A

26.25 cu.in.

Size 12 AWG – 2.25 cu. in x 5 wires = 11.25 cu. in.
Size 10 AWG - 2.50 cu. in. x 6 wires = 15.00 cu. in.
TOTAL = 26.25 cu. in.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Neon sign equipment having an open circuit voltage exceeding how many volts shall NOT be installed in or on dwelling occupancies.

A

1000 volts

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What MINIMUM size equipment grounding conductor is required for a 240-volt, single phase, 10 kW residential electric range?

A

10 AWG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Fill in the blank:

Where the NEC® specifies that one equipment shall be within sight of another equipment, the specified equipment is to be visible and NOT more than ________ distant from the other.

A

50 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Fill in the blank:

All 125-volt, single-phase, 15- and 20-ampere receptacle outlets in a dwelling must be installed in habitable rooms so that no point along the floor line is further from an outlet than ________.

A

6 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Fill in the blank:

Luminaires mounted in walls of permanently installed swimming pools shall be installed with the top of the luminaire lens NOT less than ________ below the normal water level of the pool, unless the luminaire is listed and identified for use at lesser depths.

A

18 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Fill in the blank:

Where there is no overcurrent protection on the secondary side of a 480-volt transformer with a primary current of 100 amperes, the rating of the primary overcurrent protective device should NOT exceed ________.

A

125 amperes

100 amperes x 125% = 125 amperes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Fill in the blank:

For the purpose of maintaining and servicing a 3-phase, 208Y/120-volt switchboard, a MINIMUM clear working depth distance of ________ must be maintained in front of the switchboard.

A

3 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Fill in the blank:

When a permanently installed generator is set up as a separately derived system, ________ must be provided.

A

system bonding jumper

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Fill in the blank:

Type AC cable shall provide an adequate path for ________.

A

fault-current

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Fill in the blank:

Mandatory rules of the NEC® are those that identify actions that are specifically required or prohibited are characterized by the use of the terms ________.

A

shall or shall not

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Fill in the blank:

For a direct burial feeder cable to a water well pump 50 feet from a dwelling, the NEC® approves ________ for use.

A

Type UF cable

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

True or false:

All of the following wiring methods are permitted in a ceiling space used as a return-air plenum EXCEPT rigid PVC conduit.

A

TRUE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Fill in the blank:

A 240-volt, single-phase 10 kW commercial dishwasher will draw ________ of current.

A

42 amperes

I = 10,000 watts/240 volts
= 41.6 amperes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Fill in the blank:

A type of fuse NOT permitted for new installations and shall be used only for replacements in existing installations is a/an ________ fuse.

A

Edison-base

17
Q

True or false:

All wiring methods are permitted in a ceiling space used as a return-air plenum EXCEPT Type SOW.

18
Q

Fill in the blank:

Where cord-and-plug connected appliances are likely to be used simultaneously, each ________ or fraction thereof of fixed multioutlet assemblies used in other than dwelling units, shall be considered as an outlet of not less than 180 volt-amperes.

19
Q

Fill in the blank:

All 15- and 20-ampere, single-phase, 125-volt receptacles located within at LEAST ________ of the inside walls of a permanently installed swimming pool must be protected by a Class A ground-fault interrupter.

20
Q

Fill in the blank:

A point on a wiring system at which current is taken to supply luminaires, appliances, heaters, motors and similar current-consuming equipment is considered a/an ________.

21
Q

Fill in the blank:

The MINIMUM number of 120-volt, 15-ampere, general lighting branch circuits required for a dwelling with 70 feet by 30 feet of livable space is ________.

A

Four

70 ft. x 30 ft. = 2100 sq. ft. x 3 VA = 6300 VA (house load)
120 volts x 15 amperes = 1800 VA (one circuit)
6300 VA (load)/1800 VA (circuit) = 3.5 = 4 general lighting circuits

22
Q

Fill in the blank:

Given: A branch circuit supplies a single hermetic refrigerant motor-compressor, with a FLC rating of 18 amperes, for an air conditioning unit on a dwelling unit. If 30-ampere fuses used as overcurrent protection will not carry the starting current of the unit, the rating of the fuses may be increased to a MAXIMUM value of ________.

A

40 amperes

18 amperes x 225 % = 40.5 amperes

23
Q

Fill in the blank:

According to the NEC®, lighting branch circuits must be rated based on the overcurrent protective device. The permitted load ratings for these circuits are ________.

A

15, 20, 30, 40 and 50 amperes

24
Q

Fill in the blank:

As a general rule, outside open conductors on insulators must be covered or insulated when they are within ________ of a building or structure, other than supporting poles or towers.

25
# Fill in the blank: Metal wireways shall be securely supported where run horizontally at each end and at intervals not to exceed to exceed \_\_\_\_\_\_\_\_.
5 feet