Unit 11: General Practice Flashcards

Reinforcing NEC® principles through problem-solving and application of electrical code requirements, calculations, and best practices for safe and code-compliant installations.

1
Q

Fill in the blank:

Where used outdoors, aluminum or copper-clad aluminum grounding conductors shall NOT be installed or terminated within ________ of the earth.

A

18 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Fill in the blank:

A wall-mounted central vacuum assembly connected to a single receptacle located in an attached garage of a dwelling unit shall be provided with ________ protection.

A

GFCI

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

True or False:

Where a building or structure is supplied by more than one service, a permanent plaque shall be installed at each service disconnect.

A

TRUE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Fill in the blank:

Direct and alternating current differ in that alternating current ________.

A

reverses at intervals

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Fill in the blank:

As a general rule and under normal operating conditions, regardless of the type of insulation, size 12 AWG copper conductors are permitted to be protected by an overcurrent protective device with a standard rating of NOT more than ________.

A

20 amperes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Fill in the blank:

For the purpose of service load calculations in dwelling units, each two (2) wire small appliance branch circuit shall be calculated at ________.

A

1,500 VA

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Fill in the blank:

The disconnecting means for a permanently connected appliance, rated not over 300 VA or ________, is permitted to be the branch circuit overcurrent protective device where the switch or circuit breaker is within sight from the appliance or is lockable.

A

1/8 hp

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Where a straight run of trade size 4 in. conduit containing size 2/0 AWG conductors enters and exits a pull-box and no terminations or splices are made, what is the MINIMUM required length of the pull-box?

A

32 inches

4 in. (conduit) x 8 = 32 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Fill in the blank:

Where the design and operation of a generator does not prevent overloading, the ampacity of the conductors from the generator terminals to the first overcurrent protection device shall NOT be less than ________ of the nameplate current rating of the generator.

A

115 percent

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Fill in the blank:

All single-phase cord-and-pug connected room air conditioners shall be provided with ________.

A

factory-installed AFCI, HCDI, or LCDI protection

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Fill in the blank:

The NEC® requires an equipment bonding jumper to be ________.

A

continuous

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Fill in the blank:

For Type MI cable with an outer sheath made of steel, a separate ________ shall be provided.

A

equipment grounding conductor

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Fill in the blank:

Luminaires shall be installed or constructed so that adjacent combustible materials will not be subject to temperatures in excess of ________.

A

130°F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Fill in the blank:

Luminaires containing a metal halide lamp (other than a thick-glass PAR lamp) shall be provided with a containment barrier that encloses the lamp, or shall be provided with a physical means that only allow the use of a ________.

A

lamp that is Type O

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Fill in the blank:

Unless GFCI protection is provided, luminaires and ceiling fans located over or within 5 ft. horizontally from the inside walls of an indoor installed spa or hot tub shall have a mounting height of NOT less than ________ above the maximum water level of the spa or hot tub.

A

12 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Fill in the blank:

The NEC® approves ________ for use under the accessible raised floor area of an information technology equipment room.

A
  • Type AC cable
  • rigid nonmetallic conduit
  • Type MC cable
17
Q

Fill in the blank:

The ampacity adjustment factors for conductors addressed in Section 310.15(C)(1) of the NEC® are not required to be applied when the conductors are installed in a metal wireway unless, the number of current-carrying conductors within the wireway exceeds ________ at any cross section of the wireway.

18
Q

Fill in the blank:

The voltage at the line terminals of a fire pump motor controller shall NOT drop more than ________ below the controller’s nominal rated voltage under motor-starting conditions. This limitation shall not apply for emergency run mechanical starting.

A

15 percent

19
Q

Fill in the blank:

Where a size 1/0 AWG THWN aluminum conductor is installed outdoors in a raceway with two (2) other current-carrying conductors of the same size and the ambient temperature reaches 110°F, the conductor has an ampacity of ________.

A

98 amperes

1/0 AWG AL ampacity before correcting = 120 amperes
120 amperes x .82 (temperature correction factor) = 98.4 amperes

20
Q

Fill in the blank:

Ceiling suspended (paddle) fans weighing MORE than ________ shall be supported independently of the outlet box.

21
Q

Fill in the blank:

Inverse-time circuit breakers rated at ________ or less and 1000 volts or less shall have the ampere rating molded, stamped, etched or similarly marked into their handles or escutcheon areas.

A

100 amperes

22
Q

Fill in the blank:

Where the service of a building is provided with ground-fault protection, the MAXIMUM trip time delay shall be ________ for ground-fault currents equal to or greater than 3,000 amperes.

A

One second

23
Q

Fill in the blank:

Conductor ampacity adjustment factors shall not apply to conductors in raceways having a length NOT exceeding ________.

24
Q

Fill in the blank:

The connection between the grounded circuit conductor and the equipment grounding conductor, or the supply-side bonding jumper, or both, at the electrical service of a building or structure is recognized as the ________ in the NEC®.

A

main bonding jumper

25
# Fill in the blank: Appliances require a separate disconnecting means or a unit switch with a marked “OFF” position, that is part of the appliance and will disconnect all \_\_\_\_\_\_\_\_.
ungrounded conductors