Unit 6: Voltage Drop Calculations Flashcards

Using NEC® guidelines and formulas to calculate voltage drop in conductors, ensuring efficient power distribution and minimizing energy loss in electrical circuits.

1
Q

According to Ohms Law, what is the electrical unit of current?

A

ampere

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Fill in the blank:

The NEC® definition of ________ is “connected to establish electrical continuity and conductivity”.

A

bonded (bonding)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Fill in the blank:

In addition to the number of 120-volt, single-phase branch circuits required in other areas of a dwelling, at least one additional ________ branch circuit shall be provided to supply the laundry outlet in the laundry room.

A

20-amperes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Fill in the blank:

Where rigid metal conduit (RMC) or intermediate metal conduit (IMC) is threaded in the field where corrosion protection is necessary, the threads shall be coated with a/an ________ compound.

A

approved electrically conductive, corrosion-resistant

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Fill in the blank:

In a straight run of rigid Type PVC conduit, expansion fittings are to be provided to compensate for thermal expansion and contraction where the length change is expected to be at least ________ or greater.

A

1⁄4 in.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is permitted in the dedicated electrical space above a panelboard?

A

leak protection and sprinkler protection

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Fill in the blank:

For other than submersible types of motors, they shall be located so that adequate ________ is provided and so that maintenance, such as lubrication of bearings and replacing of brushes, can be readily accomplished.

A

ventilation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Fill in the blank:

For bathtub and shower areas, no parts of cord-connected luminaires, lighting track or ceiling-suspended (paddle) fans shall be located within a zone measured ________ horizontally from the top of the bathtub rim or shower stall threshold.

A

3 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Fill in the blank:

Given: After all demand factors have been taken into consideration, a one-family dwelling with a 120/240-volt, single-phase electrical system has a demand load of 35,000 VA. The MINIMUM size THWN copper phase conductors required for an underground installed service is ________.

A

2 AWG

I = 36,000 VA/240 volts
= 145.8 amperes x .83
= 121 amperes

Size 2 AWG copper conductors with an ampacity of 125 amperes should be selected from Table 310.12.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

True or False:

In general, when sizing the overcurrent protection, disconnect size, and supply circuit conductors for a motor used in a continuous-duty application, they shall be sized based on the full-load running current of the motor given in the Tables of the NEC.

A

TRUE

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Fill in the blank:

Continuous-duty motors, more than one hp, with a marked service factor less than 1.15 shall have the MINIMUM running overload protection sized at ________ of the nameplate rating of the motor, where modification of this value is not necessary.

A

115 percent

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Fill in the blank:

Mobile home service equipment shall be located in sight from and NOT more than ________ from the exterior wall of the mobile home it serves.

A

30 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Fill in the blank:

As a general rule, switches or circuit breakers shall ________.

A

not disconnect the grounded conductor of a circuit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What is the MINIMUM number of 120-volt, 20-ampere, single phase branch-circuits that must be provided to supply receptacle outlets in dwelling units?

A

five

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Fill in the blank:

Small gage conductors such as a single size 16 AWG conductor is permitted to carry continuous loads up to ________, as long as the conductor is protected by a fuse or circuit breaker.

A

8 amperes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Fill in the blank:

The accessible portion of abandoned supply circuits and interconnecting cables located in an information technology equipment room shall be removed, UNLESS ________.

A

contained in a raceway

17
Q

Fill in the blank:

Generally, in dwelling units, where one or more lighting outlets are installed for interior stairways, there shall be a wall switch at each floor level, and landing level that includes an entryway, to control the lighting outlets where the stairway between floor levels has at LEAST ________ risers or more.

18
Q

Fill in the blank:

A receptacle installed outdoors in a location protected from the weather or in other damp locations shall have an enclosure for the receptacle that is ________ when the receptacle is covered (attachment plug cap not inserted and receptacle covers closed).

A

weatherproof

19
Q

True or False:

A fused disconnecting means for motor circuits rated 1000 volts or less, shall have an ampacity of at LEAST 115 percent of the full-load current rating of the motor it disconnects.

20
Q

Determine the current, in amperes, on the circuit conductors for a 208Y/120-volt, 3- phase system where each phase is balanced with a 2,500 VA load and the total load is 7,500 VA.

A

20.82 amperes

I = VA ÷ volts x 1.732
I = 7,500 VA/208 x 1.732
= 7,500/360.25
= 20.82 amperes

21
Q

Fill in the blank:

No overcurrent device shall be connected in series with any conductor that is intentionally grounded, unless the overcurrent device or circuit breaker ________.

A

simultaneously opens all conductors of the circuit including the grounded conductor

22
Q

Fill in the blank:

For temporary wiring installations that have an assured equipment grounding conductor program, all required tests shall be performed at intervals NOT exceeding ________.

23
Q

Fill in the blank:

For continuous-duty motors, the motor nameplate current rating is used to determine the size of the ________ required for the motor.

A

motor overload protection

24
Q

Fill in the blank:

GFCI protection for personnel is required where a 125-volt, single-phase, receptacle is located on a wet bar countertop if within ________ from the top inside edge of the bowl of the sink.

25
# Fill in the blank: Boxes shall be closed by suitable covers securely fastened in place. An underground metal box cover that weighs over \_\_\_\_\_\_\_\_ shall be considered meeting this requirement.
100 pounds