Unit 1: Pie Circle Formulas Flashcards

Understanding the relationship between power, voltage, current, and resistance using Ohm’s Law and Watt’s Law, applying circular formulas (P=VI, V=IR, etc.) to electrical calculations for the Master Electrician 2020 exam.

1
Q

Fill in the blank:

Where multiple driven ground rods are installed at a service, they shall be spaced NOT less than ________ apart.

A

6 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Fill in the blank:

Where a one-family dwelling has a 200 ampere,120/240-volt, single-phase main service panel and is being supplied with size 2/0 AWG THW copper ungrounded (line) service-entrance conductors in rigid metal conduit (RMC), the MINIMUM required size of the bonding jumper for this service-entrance conduit is ________ copper.

A

4 AWG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Fill in the blank:

A disconnect switch enclosure installed in a Class II, Division 2, hazardous location in an industrial establishment shall be ________.

A

dusttight

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Fill in the blank:

The interior of enclosures or raceways installed underground shall be considered to be a ________ location.

A

wet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Determine the ampacity of four (4) size 1/0 AWG THW copper current-carrying conductors installed in a common raceway with an ambient temperature of 86 degrees F.

A

120 amperes

Size 1/0 AWG THW ampacity = 150 amperes before adjusting 150 amperes x 80% (adjustment factor) = 120 amperes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Fill in the blank:

The NEC® defines a continuous load to be a load where the maximum current on the circuit is expected to continue for at LEAST ________ hours or more.

A

three

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Determine the MINIMUM size THW copper branch-circuit conductors the NEC® requires to supply a 3-phase, continuous-duty, ac motor that draws 70 amperes per phase. Consider all terminations are rated for 75 deg. C.

A

3 AWG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Given: You have determined a conductor has a computed ampacity of 75 amperes. What is the MAXIMUM standard ampere rating of the overcurrent protection device the NEC® permits to protect this circuit here this is not a motor circuit or part of a multioutlet branch circuit supplying more than one receptacle?

A

80 amperes

FLC of motor = 70 amperes x 125% = 87.5 amperes
Size 3 AWG THW with an ampacity of 100 amperes should be selected.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Fill in the blank:

A 208-volt, 3-phase, 50 hp, squirrel-cage, continuous-duty, ac motor has a full-load running current rating of ________.

A

143 amperes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the MAXIMUM distance that a disconnect switch is permitted to be located from the operator’s station for a portable carnival ride?

A

6 feet

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Determine the MINIMUM trade size electrical metallic tubing (EMT) required to enclose eight (8) size 6 AWG copper conductors with THHW insulation, when installed in a 50-foot conduit run.

A

1 1⁄4 in.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Fill in the blank:

Where exceptions are not applicable, when a feeder supplies a continuous load of 240 amperes, the overcurrent protection device protecting this feeder circuit shall have a rating of at LEAST ________.

A

300 amperes

240 amperes x 125% = 300 amperes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Fill in the blank:

Liquidtight flexible metal conduit (LFMC) shall be securely fastened in place WITHIN ________ of each box or other conduit termination.

A

12 inches

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Fill in the blank:

When a pull box or junction box contains conductors of size 4 AWG and larger and a straight pull of the conductors is to be made, the length of the box shall NOT be less than ________ times the trade diameter of the largest conduit entering the pull box or junction box.

A

eight

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

Fill in the blank:

Conduit nipples not over 24 inches long may be filled to a MAXIMUM of ________ of their cross sectional area.

A

60 percent

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Determine the MAXIMUM number of size 14 AWG THHN conductors permitted to be installed in a trade size 3/8 in. flexible metal conduit (FMC) that contains a bare size 14 AWG grounding conductor, when the FMC has external fittings.

17
Q

Fill in the blank:

According to the NEC®, conductors supplying wet-niche underwater pool luminaires must be enclosed in ________.

A

schedule 40 rigid polyvinyl chloride conduit (PVC)

18
Q

Fill in the blank:

Underground wiring is not permitted under a permanently installed swimming pool or within ________ of the pool, unless the wiring is supplying the associated pool equipment.

19
Q

Fill in the blank:

The NEC® does NOT permit ________ batteries as a source of power for emergency systems.

A

automative

20
Q

Fill in the blank:

In new installations, the MINIMUM clear working space the NEC® requires between a 480Y/277- volt, switchboard and a 480-volt motor control center when facing each other is ________.

21
Q

Fill in the blank:

In the guest rooms of hotels, motels, and sleeping rooms of dormitory units a MINIMUM of ________ 125-volt, 15- or 20-ampere, general purpose receptacles installed in the room is/are required to be readily accessible.

22
Q

Fill in the blank:

When branch circuit conductors are installed inside a ballast enclosure of a luminaire and are within three (3) inches of the ballast, the conductors shall have a temperature rating NOT lower than ________, unless supplying a luminaire marked as suitable for a different insulation temperature.

23
Q

Fill in the blank:

When size 4 AWG or larger conductors enter a panelboard, ________ must be provided.

A

an identified bushing or threaded hub

24
Q

Fill in the blank:

Class ________ locations are those that are hazardous because of the presence of easily ignitable fibers or where materials producing combustible flyings are handled, but in which such fibers/flyings are not likely to be in suspension in the air in quantities sufficient to produce ignitible mixtures.

25
# Fill in the blank: A single-phase, 240-volt, 15 kVA standby generator may be loaded to a MAXIMUM of \_\_\_\_\_\_\_\_ per line.
62.5 amperes