UL 142: Steel Aboveground Tanks for Flammable and Combustible Liquids Flashcards

1
Q

What is the minimum thickness allowed for the flanged section of a pressed steel fitting? (refer to No. 3 of Figure 7.1 for an illustration of this type of fitting) (UL 142, Table 7.4)

A

0.135 in.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the minimum length of thread required for threaded pipe connections that are 2.5 to 3.5 inches in diameter? (UL 142, Table 7.4)

A

1 inch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What is the minimum length of thread required for a threaded pipe connection that is one inch in diameter? (UL 142, Table 7.4)

A

5/8 inch

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Each primary containment tank and each compartment of a compartment tank shall have provision for what kinds of venting? (UL 142, Section 8.1)

A

Each primary containment tank including each compartment of a compartment tank shall have provisions for both normal venting and emergency venting.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

The interstitial space of a secondary containment tank shall have provisions for what type of venting? (UL 142, Section 8.1.2)

A

The interstitial space of a secondary containment tank shall have provisions for emergency venting.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

According to UL 142, if a horizontal steel aboveground tank has a diameter of six feet, what is the maximum length of the tank? (UL 142, Section 13.1.2)

A

The overall length of a horizontal tank shall not be greater than six times its diameter with a maximum of 72 feet, therefore 36 feet for a tank 6 feet in diameter.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Under what condition would the flanged flat head of horizontal tank more than 72 inches in diameter need an additional brace welded to the tank head? (UL 142, Section 13.3.3)

A

If it is made of steel that is less than 5/16 in (7.9 mm) thick.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

According to UL 142, what is the minimum diameter allowed for a vertical cylindrical steel tank that is 20 feet tall? (UL 142, Section 15.1.1)

A

The minimum diameter of a vertical tank shall not be less than one-quarter of its height. Therefore, a 20 foot tall tank should be at a minimum 5 feet in diameter.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What is the maximum allowable shell height for a vertical cylindrical steel tank constructed according to UL 142? (UL 142, Section 15.1.2)

A

The shell height of a vertical tank shall not be more than 50 feet (15.24 m) and not to exceed 60,000 gallons of capacity.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly