Tools 1 Flashcards

1
Q

Extinguishers - General Info

A
  • Operating psi = 100psi @ 70 degrees (Water)
  • Wt: 30 lbs. (Purple K = 52 lbs; AFFF = 30 lbs)
  • Capacity: 2-1/2 Gals ( Purple K = 27 lbs Dry Chem; AFFF = 2-
    1/2 Gals Water/10 oz. foam)
  • Range: AFFF = 35’-40’; Purple K = 19’-20’
  • Discharge Time: 55 seconds ( Purple K = 11 Seconds)
  • Coverage: Purple K = 30 sq ft.
  • NEVER >. 125psi (Water Only)
  • Freezes at 32 degrees ( Water & AFFF only)
    • PurplemK = -40 degrees to 120 degrees
  • Insp. daily & after each use (Water only)
    • Purple K = Insp beginning of each tour & MONTHLY
      (thoroughly examined)
    • AFFF = Insp Daily
  • Hydrostatically tested @ 5 year intervals OR if any corrosion OR
    mechanical damage (Water only)
  • AFFF: If not used w/in 1 YEAR, Empty/refill/recharge
  • Purple K: If not used &/or recharged w/in 6 MONTHS =
    Discharge & Recharge
  • Purple K: Ht.= 22-3/4”; Nozzle = High Velocity
How well did you know this?
1
Not at all
2
3
4
5
Perfectly