Temperatures Flashcards
Reconstruction - Base metal temp where welding is not allowed
< 0 F
653: 10.4.2.3
Reconstruction - Base metal temp when hand-warm pre-heat is required
0 - 32 F
653: 10.4.2.3
Linings - Minimum temp when installing tank bottom linings
5 F above
dew point
652: 8.3
Corrosion – The corrosion rate of steel tank bottoms may double with this rise in temperature
18 F
651: 5.4.1 Note
UT Calibration - Calibration Block must be within what temperature of the part to be examined
25 F
577: 8.9.3.1
Corrosion – CUI temperature range for CS & 400 Series SS
10 - 350 F
571: 3.22.3.a.1
Vacuum Box - Standard temperature range for VB exam
40 - 125 F
650: 8.6.6
PT - Standard temperature range for a PT exam
40 - 125 F
V: T-652/653
Impact Test - Design metal temperature that requires weld procedure used for vertical welds to be impacted tested
< 50 F
650: 9.2.2.3
Brittle - Tank metal temperature where brittle fracture is NOT a concern
> 60 F
653: Fig 5.1
Bottom Lap Patches - Metal temp where lap-patches are NOT allowed in critical zone on SS tank
> 100 F
653: 9.11.1.2.3
Intervals - If tank product solidify below this temperature, the code maximum interval rules do not apply
< 110 F
653: 6.4.2.1.2.1
Corrosion – CUI temperature range for 300 Series SS
140 - 350 F
571: 3.22.3.a.2
Corrosion - Temperature when high strength caustic causes general corrosion in CS. Both API 571 & 575 answers
> 150 F
170 F
575: 8.4.4
571: 3.14.3.b
Corrosion - Most aggressive temperature range for CUI.
170 – 230 F
575: 8.2.8