Linings - Typically anchor profile of steel surface required for the installation of a tank bottom lining
1.5 – 4.0 mils
Reference: 652: 7.5
Welds - Maximum undercut of a vertical weld & nozzle weld
1/64”
Reference: 650: 8.5.2.b
Welds - Maximum undercut of a horizontal weld
1/32”
Reference: 650: 8.5.2.b
Welds - Maximum diameter of a surface porosity cluster
3/32”
Reference: 650: 8.5.2.c
Weld Qualification - Max allowed discontinuity in a Bend Test
1/8”
Reference: IX: QW-163
Nameplates - Minimum size of nameplate letters
5/32”
References: 650: 10.1.1 & 653: 13.1.1.1
Bottoms - Minimum external projection of bottom plate on an existing tank (from toe of shell-to-bottom FW)
3/8”
Reference: 653: 4.4.5.7
Repairs - Max amount of peaking or banding allowed
1/2”
Reference: 650: 7.5.4.a & b
Reconstruction - Max amount of peaking allowed in vert welds
1/2”
Reference: 653: 10.5.4
Shell Calcs – When calculating tmin for shell LTA, minimum distance away from a weld where “E” is always 1.0
> 1” or 2t
Reference: 653: 4.3.3.1 (definitions)
Shell Patch - Minimum overlap of shell lap-patch used to cover a hole (edge of hole to edge of patch)
1”
Reference: 653: 9.3.2.3
NDE - When performing a PT examination, minimum distance to clean beyond the area to be examined
1”
Reference: V: T-642.b
NDE - When performing a MT examination, minimum distance to clean beyond the area to be examined
1”
Reference: V: T-741.1.b
Reconstruction - Maximum amount of banding allowed in a horizontal welds
1”
Reference: 653: 10.5.5
Bottoms - Min overlap required for single-welded lap joints
1”
Reference: 650: 5.1.3.5
Bottoms - Minimum external projection of bottom plate on a new tank
2”
Reference: 650: 5.4.2
Vacuum Box - Minimum overlap of previously test surfaces when using a vacuum box
2”
Reference: 650: 8.6.5
Bottom Patch - Minimum overlap of bottom lap-patch used to cover corroded area (edge of corrosion to edge of patch)
2”
Reference: 653: Fig. 9.13
Bottom Patch - Minimum distance bottom lap-patch fillet weld to the nearest existing bottom weld
2”
Reference: 653: Fig. 9.13
Shell Patch - Minimum radius of a shell lap-patch
2”
Reference: 653: 9.3.1.4
Reconstruction - If reusing bottom plates, min distance to cut from existing bottom welds (if plates are not deseamed)
2”
Reference: 653: 10.3.2.1
Reconstruction - If reusing roof plates, min distance to cut from existing roof welds (if plates are not deseamed)
2”
Reference: 653: 10.3.4.1
Shell Pitting - Maximum allowed vertical length of pits on a tank shell (amount below corrosion allowance)
2” in 8” line
Reference: 653: 4.3.2.2.b
Bottom Pitting - Maximum allowed length of pits in the critical zone that can be repaired by weld-buildup
2” in 8” arc
653: 9.11.1.6.a
Bottoms - Radial length of critical zone measured from shell
3”
653: 3.11
Bottoms – Suggested sand pad thickness
3-4”
650: B.3.2
Welds - Min distance between clusters of surface porosity
4”
650: 8.5.2.c
Shell Patch - Minimum dimension of a shell lap-patch
4”
653: 9.3.1.7
Shell Patch - Minimum radius of a shell flush-patch
6”
653: Fig 9.1 “R” dimension
Shell Calcs – When calculating tmin for shell LTA, minimum distance away from a rivet where “E” is always 1.0
6”
653: 4.3.4.1
Bottom Patch - Minimum size of bottom lap-patch that does NOT cross a bottom seam
6”
653: 9.11.1.1.c
Bottom Patch - Minimum distance between a bottom lap-patch and the shell for patches that do NOT extend to the shell
6”
653: Fig 9.13
or 9.11.1.2.b
Reconstruction - If reusing shell plates, min distance to cut from existing shell welds (if plates are not deseamed)
6”
653: 10.3.3.1.c
RT - Minimum diagnostic length of a RT for vertical or horizontal welds
6”
650: 8.1.2.8
653: 12.2.1.7
Weld Qualify - Minimum weld length when qualifying a welder with RT/UT using a coupon or 1st production weld
6”
IX: QW-302.2
IX: QW-304.1
Weld Qualify - Minimum weld length when qualifying a welding operator with RT/UT of a test coupon
6”
IX: QW-302.2
Shell Patch – Minimum distance to overlap a shell weld when using a lap-patch
6”
653: 9.3.1.5
Corrosion – Area to dig when checking for soil-to-air corrosion
6 – 12”
575: 8.2.11.1.1
NDE – Distance of eye-to-part to count as a Visual Exam
6 - 24”
577: 8.3.1.f
Vacuum Box - Typical size of a vacuum box
6” x 30”
650: 8.6.1
Shell Patch - Minimum dimension of a shell flush-patch
12”
653: 9.2.2.1
Bottoms - Minimum dimension that a 3-lap joint can be from: other 3-laps, the shell, or annular plate joints
12”
650: 5.1.5.4.2
Bottom Patch - Minimum dimension of bottom lap-patch that crosses a bottom seam
12”
653: 9.11.1.1.a
Foundations - Suggested height above grade for new tank bottoms
12”
650: B.3.1
Shell Patch - When adding a shell flush-patch that extends to a horizontal shell weld, minimum distance to cut the
horizontal weld past the new vertical welds
12”
653: Fig 9.1
Note 2
Shell Patch - Dimension of a shell flush-patch that is considered either a major repair or alteration
> 12”
653: 3.26.c
Definition - Dimension of a shell vertical weld if repaired or replaced is considered a major repair or major alteration
> 12”
653: 3.26.e
Bottom Patch – Max width of bottom patch in the critical zone
24”
653: 9.11.1.2.i
Bottoms - Minimum radial width of annular plate (distance between shell and nearest bottom fillet weld)
24”
650: 5.5.2
Hot Tap - Minimum height of liquid above new nozzle during the hot tap operation
36”
653: 9.15.1.2
Weld Qualify - Minimum weld length when qualifying a welding operator with RT/UT of first production weld
36”
IX: QW-305.1
NDE - Length of sweep board used when checking for banding or peaking
36”
653: 10.5.4 / 5
Welds - Maximum distance between welder ID stamps on a tank weld
36”
650: 9.4
653: 11.2.2
Shell Patch - Maximum size of shell lap-patch (vertical & horizontal dimensions)
48” x 72”
653: 9.3.1.7
Settlement - Maximum distance between tank settlement survey points across the inside of the tank
10’
653: Fig B.2
Roofs – Maximum shunt spacing on floating roofs
10’
650: C.3.1.6
CP – Typical tank size for Galvanic CP systems
< 20’
651: 6.2.1
Settlement - Maximum distance between tank settlement survey points around the outside diameter of the tank
32’
653: Fig B.1 / 12.5.2
NDE - Maximum distance between RT’s in horizontal welds when welding to existing shell plates
50’
653: 12.2.1.2 b&c
Shell Calcs - Tank diameter when Variable Point Design method should always be used to calc shell minimum thickness
> 200’
653: 4.3.3.4
Shell – Minimum offset between vertical welds in adjacent courses
5t
650: 5.1.5.2.b
Bottoms – Minimum size of bottom welds
Full Fillet
650: 5.1.5.4.3