Static Pressure Transmitter Calibration Rosemont 3051 Flashcards

1
Q

What is the accuracy of pressure measurements required?

A

+/- 3.0 psi for crude/products and +/- 1.0 psi for chemicals.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

How often should pressure transmitters be verified?

A

Monthly

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

How often should the pressure transmitters be calibrated?

A

Annually

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How many points across the range of operation should the pressure transmitters be verified?

A

Three points across the range of operation.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

How accurate must the Digital Multimeter (DVM) be?

A

0.5% accuracy (NIST Traceable)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Who should be notified before performing calibration check?

A

The control Center

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What should be done to the flow computer before calibration?

A

The flow computer must be set to Manual or Fixed mode and insure that manual or fixed mode will not result in any unsafe conditions.