Bi-directional Meter Proving Flashcards
What is the tolerance (percentage) of flow rate between the last Prove?
10%
What is the allowable gravity change between last prove and current? (degrees API)
2 degrees API
What is the maximum allowable temperature difference (deg. F) between the last and current Prove.
10 deg. F
What is the maximum allowable pressure change (psig) between the last prove and the current?
20 psig
What is the frequency of Proving compared to bbls flow rate per month?
0-5000 90-105, 5000-7499 60-75, 7500-999,999 30-42, over 1 million 15-30 days. Add 15 days to each for the range.
Name the parts of a bi-directional meter prover.
Reciever trap, displacer (ball), switch, 4-way diverter valve, electronic pulse counter, pulse generator, meter, double block valve,
How long do you perform a manual pulse count?
36 seconds
What do you multiply a manual pulse count to get bbls/hr?
Multiply by 100
What is the minimum consecutive repeatability between 5 out of 6 consecutive runs?
0.05%
How many sets of runs must you perform and fail before contacting supervisor?
Two sets of runs
What is the formula for checking repeatability percentage?
(maximum-minimum) / minimum * 100=repeatability %
What is the nearest temperature average allowed when recording during proving?
0.1 deg. F
What is the nearest pressure average allowed when recording during proving?
1 psi
What two things should be checked after diverting flow through the prover?
Check for leaks at all critical valves, and assure no air or gas is in the prover.