SSPS Flashcards
What does the Bistable Test Switch in test do?
- Gives SSPS a trip signal for both trains
- Used to place bi-stable in “Trip” (if it fails in its non trip direction)
What does the RPS Bypass Switch in bypass do?
- Prevents getting a trip signal
- Puts power to logic bay regardless of input, allowing you to test the input drawer (using bistable test switch) without chance of causing an actuation.
(keyed switch)
What powers Train A Slave Relays?
CRID I
(120v AC)
What powers Train B Slave Relays?
CRID IV
(120v AC)
What power failure will prevent an actuation of ESF equipment?
- A loss of either CRID I or CRID IV (Train Specific) will prevent an ESF actuation
- (Master and Slave Relays are normally de-energized. Loss of a supplying CRID won’t allow the SLAVE Relays to energize on a trip)
Where does the SSPS General Warning come from?
Logic Cabinets
What will cause an SSPS General Warning?
- Bypass Bkr Closed
- Output mode selector switch in test
As well as: - Loss of 48v DC or 15v DC (CRID lost)
- Input Error inhibit switch in INHIBIT
- Multiplexer switch in INHIBIT
- Any circuit board removed except isolation boards
- Permissive switch out of OFF
- Memories switch out of OFF
- Grounded return fuse blown
A loss of which SSPS power supplies will cause a Rx trip?
Both 15v DC pwr supplies
OR
Both 48v DC pwr supply
How do the Trip Coils on the RTBs cause the Reactor Trip Breakers to trip?
Energize to trip
How do the UV Coils on the RTBs cause the RTB to trip?
Deenergize to Trip (loss of 48v DC)
does NOT need control power
How do the Rx Trip switches trip the Rx?
Either Rx Trip Switches will energize both Rx Trip and Bypass Breaker Trip Coils (all 4)
What does the Shunt Coil do for the RTB?
Energizes the trip coil
(RTBs only, they are not on the Rx Trip Bypass Bkrs)
uses control power
If both Rx Trip Bypass Bkrs are closed in at the same time, what will happen?
Trips both Bypass Breakers
If you put bistable test switch to test, what happens?
Trips (actuates) bistables with the exception of CTS
(CTS bistables are bypassed. They are energize to actuate)
What is provided power directly from the SSPS Input Bays?
Input Bay Direct Feeds
What are the Input Bay Nondirect feeds powered by?
Protection racks
Is the General Warning light visible with the Logic Cabinet door closed?
Yes, it is visible on the Logic Bays
Which RTB and Rx Trip Bypass Bkrs are tripped by Train A SSPS?
- Rx Trip Bkr A
- Rx Trip Bypass Bkr B
Which RTB and Rx Trip Bypass Bkrs are tripped by Train B SSPS?
- Rx Trip Bkr B
- Rx Trip Bypass Bkr A
What will happen if you get a General Warning on Both Trains of SSPS?
Reactor will trip
What does the Isolation Amplifier do?
Ensures failure in control system does not cause the same issue in the protection system
If the Output Mode Selector Switch is taken to test, what happens?
Disables all slave relays for an entire train
(by replacing 120 vAC power with 15 vDC)
What does the Input Error Inhibit Switch do?
Keeps logic cards from sensing a change in input. The signals will NEVER get to the logic cabinet, which allows testing.
SI Switch for that Train WILL work
What does the MULTIPLEXOR DO?
Only goes to status lights, alarms, PPC