EDG AUX Flashcards

1
Q

What happens to the EDG ventilation system when outside air temp is < 45°?

A

Tempering dampers open to stop drawing in cold outside air

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

When do the EDG Supply and Exhaust fans stop?

A
  • Stop 30 min after EDG shutdown
  • 70°F Room Temp
  • On acutation of CO2
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

How often does the gear lube oil ctrl valve open while the EDG is in stby?

A

Solenoid opens every 4 hours for 2 min

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

When do the gear lube oil ctrl valves open when the EDG is started?

A

Immediately on the start of the EDG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

When do the gear lube oil ctrl valves close after the EDG is shutdown?

A

8 min after an EDG is shutdown/tripped

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What provides fuel to the EDG while its running?

A

Shaft Driven Fuel Oil Pump

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

When is the field flash disabled?

A

80% speed during a fast start

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What must the Throttle Control Cylinder have to be able to open?

A

Ctrl Air

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

When does the supply fan for the EDG Auto start?

A
  • 20 Sec after an EDG start
  • 95°F Room Temp
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

When does the exhaust fan for the EDG Auto start?

A
  • EDG start
  • 95°F Room Temp
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

What is the minimum required level of each Fuel Oil Storage Tank?

A

≥ 46,000 gal to supply 1 EDG for 7 days at full load per LCO 3.8.3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What is the minimum level in the Fuel Oil Day Tank per SR 3.8.1.4?

A

101.4 gal

(15 minutes worth run time at full load)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What are the designed temp bases for the EDG room?

A

< 104°F in standby
< 130°F running

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

When does the Stby EDG JW Pump auto start?

A

Low # (16 psig)

10 sec time delay

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What temp does the EDG Aux Jacket Water Heater maintain the EDG Jacket Water at?

A

145°F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Unit 1 is at 100% power. A relief valve has failed open on 1AB Emergency Diesel Generator Starting Air Receiver #1. The associated starting air compressor has tripped off. What is the response of 1AB Emergency DieselGenerator if a start signal occurs before any operator action? The EDG will …

A

start in the normal time from #2 Starting Air Receiver but only one starting air valve will supply all of the cylinders with starting air pressure.

17
Q

Upon a loss of control air, EDG air aftercooler regulating valves fail to what position?

A

Fails to allow full flow through the EDG air aftercooler

18
Q

What is the makeup water to the EDG JW surge tank?

A

Demin water

19
Q

What is the Emergency Backup source of water to the EDG Jacket Water System?

20
Q

Can the before and after pump supply the EDG while its running if the Shaft Driven oil Pump fails?

A

No. The B and A Pump capacity is insufficient for continued EDG operation.

21
Q

EDG Valve Gear Lube Oil valves fail how on a loss of Ctrl Pwr?

22
Q

How many starting air valves do you need to start a diesel?

A

only 1 starting air valve is needed and 1 receiver

Starting air lines and receivers are x-tied

23
Q

Do both starting air valves open on a diesel start?

24
Q

What is the cooling supply to the EDG Woodward Electronic Governor?

A

Jacket Water

25
Are the fuel oil transfer pumps designed for a staggered start based on day tank level?
NO! Both pumps are designed to start at the same level.
26
What auxiliary EDG items are supported/cooled by ESW?
Jacket Water Lube Oil Intake Air After Coolers Emergency Makeup to Jacket Water
27
What is the purpose of the before and after pump?
Maintains positive oil pressure until Engine-Driven takes over operation
28
Is EDG Operability affected by a Failure of Shaft Driven LO Pump?
YES! INOPERABLE