SI (Safety Injection) Flashcards
ECCS purpose
Emergency Core cooling system
- Deliver cooling water to the reactor core in the event of a LOCA.
- Limits the fuel cladding temp. and thereby ensures that the core will remain intact with its heat transfer preserved.
Actions Caused by an SI signal
- Rx Trip
- EDG startup
- FW Isolation
- AFW auto-start
- Safeguard sequencer actuation
- Phase A
- CV Ventilation isolation
- Control room pressurization
- Closes normal Dampers on HVH-1,2,3,4
System flowpaths for injection phase and psig
- Injection from RWST by SI pumps (1500psig)
- Passive Accumulator injection (630psig)
- Injection from RWST by RHR pumps (130psig)
At what % in the RWST do we move to Recirculation phase?
-9% in the RWST. Changes from RWST feeding pumps to CV sump feeding pumps via the RHR pumps
Long Term Recirculation phase implements at what time?
-11 hours after the LOCA
SI signals
- Manual
- Low PZR pressure (1715psig)
- High Differential Steam line pressure (100psid 1/3 Loops)
- High Steam line flow on 2/3 S/Gs (37.25-109% from 20-100%power)
- High CV press (4psig)
- Hi Hi CV press (10psig)
Hi-Hi CV pressure causes what?
-CV spray actuation
What pumps start on SI signal?
- CV spray pumps (10psig CV)
- RHR pumps
- SI Pumps
What Valves reposition on SI signal?
- SI-870A/B(Bit Outlet) open
- RHR-744A/B (RHR cold leg injection) open
What valves get the SI signal?
- SI-867A/B (Bit inlets)
- SI-870A/B (Bit outlets)
- SI-841A/B (BIT recirc to BAST)
- SI-865A/B/C (Accumulator Outlets)
- RHR-744A/B (RHR cold leg injection)
SI-864 A/B
RWST Discharge valves
location, and when they close?
- Located in SI Pump Room West wall
- Normally open.
- Isolates RWST when below 9%
SI-866A/B
Hot Leg Injections from SI pump
- Normally closed
- “Backwards” power. A-MCC6, B-MCC5
- Used after 11 hours after recirc to avoid boron buildup.
SI-865A/B/C
Accumulator MOV isolations
- Normally open
- Closed when RCS is cooled down or depressurized for maintenance.
- receive SI signal but don’t reposition
RWST
Capacity, Boron concentration and Temp
- 353,000gal
- 1950ppm Boron
- 45-100F
How many seconds after SI signal do SI pumps start on sequencer?
-5 secs