SH Flashcards
Screen House Function
(three things)
-Provide reliable supply of river water for Secondary Service, Nuke Service, Decay River, Reactor River, Fire Service, and Screen House Ventilation/Cooling
-Bar Rake and Screen system ensures river debris is removed prior to reaching pump suctions.
-River water pump lubrication system (RWPLS) provides river pump bearing lubrication and cooling under normal conditions.
Three (3) Automatic Bar Rakes
(SR-S-2A/B/C)
Function, auto signals, interlock
Function: remove >1” debris
Auto signal: Tork timers @ 0700, 1500, and 2300 OR DP of 4” (A &C only)
Interlock: Slack cable event causes rake to STOP
Three (3) Traveling Screens
(SR-S-3A/B/C)
Function
Moving screens downstream of bar rakes remove debris >3/8” square. Cleaned
by water jet spray directed down on screens during ascending run
Three (3) Traveling Screens
(SR-S-3A/B/C)
Start Permissive
Start Permissives: Requires 67# screen wash pressure to start, will NOT run without SWPs
Three (3) Traveling Screens
(SR-S-3A/B/C)
Auto Signals
Rake Starts, Tork timers @ 0300, 1100, and 1900 or DP of 4” (A & C only)
Three (3) Traveling Screens
(SR-S-3A/B/C)
Speed Control
SLOW (2.5ft/min) speed in HAND, FAST (10ft/min) speed on high DP of 6”
Screen Wash pumps (SW-P-1A/B)
Function
Provide high pressure water for cleaning screens and sluicing debris to trash pits.
Screen Wash pumps (SW-P-1A/B)
Power Supply
1R 480V Bus/1T 480V Bus, 125 vital DC control power
Screen Wash pumps (SW-P-1A/B)
Auto start/interlocks
Auto Start: screen/rake demand relays
Interlocks: First SW-P-1 taken out of PTL (placed in standby) is lead pump (will start first
on demand signal)
Screen Wash pumps (SW-P-1A/B)
Trips
Load shed on ES and locked out by 27/86 w/ manual reset, Loss of DC Control Pwr
Tech Specs from L&P for rake and screen
Rake and screens satisfy TS definition of auxiliary equipment needed for safety related TS river water pumps, OPERABILITY based on DP <6”
Time limit on rake and screen continuous operation brings in alarm and indicates elevated river debris?
15 min rake and 20 min screen
Screen Wash strainer (SW-S-1A/B)
Power supply
1A/1B SH ES MCC
Screen Wash strainer (SW-S-1A/B)
Auto Signals
AUTO start with pump start, Backwash @ 9# with a 10# DP alarm
Screen Wash strainer (SW-S-1A/B)
Interlocks
Strainer backwash valves OPEN on high DP and timer
Two (2) River Water Lubrication Pumps (WT-P-33A/B)
Function
Provide clean filtered water (Domestic Water is backup) to river pumps
for bearing lubrication and flushing. Bearing temp < 155o
F @ >95# and >20gpm
Two (2) River Water Lubrication Pumps (WT-P-33A/B)
Power supply
1A/1B ES SH MCC
L&P for Screen House
2 main things
1.) Min lube water pump flow is 20 gpm for WT-P-33A/B protection
2.) If lube water is not available or if there is no packing leak off SW pumps can perform design function (self-lubricating)
Abnormal system operation
River water low level for system failure and RX trip
RW system failure if river <277’
Trip RX at <271’
Abnormal operation
What happens on failure of York Haven Dam
All river pumps retain suction