IA Flashcards
system pressure order
1
component/position, cycle pressure, PS, Cooled by, temp trip, time unloaded
100-115# = IA-P-4 Cycles
power supply = 1J 480V BUS
cooled by SCCW
428°F = Trip
20 minutes unloaded = Auto Shutdown
2
component/position, cycle pressure, cycle off what? PS, cooled by? swap to what/when? temp trip, time unloaded/action
100-110# = IA-P-1A/B Cycle IF IN HAND (lead)
power supply = 1A/B ES MCC
cycle off receiver pressure
cooled by SCCW, swap to FS on all 3 SC pump breakers open
425°F = Trip
5 minutes unloaded = Auto Shutdown
3
component/position, cycle pressure, cycle off what? PS, cooled by? swap to what/when? temp trip, time unloaded
95-105# = IA-P-1A/B Cycle IF IN Auto (normal)
power supply = 1A/B ES MCC
cycle off receiver pressure
cooled by SCCW, swap to FS on all 3 SC pump breakers open
425°F = Trip
5 minutes unloaded = Auto Shutdown
4
component/position, cycle pressure, cycle off what? PS, Cooled by?, temp trip, time unlaoded, normally in what?
90-100# = SA-P-1A Cycles
power supply = 1C 480V TP MCC
cycle off receiver pressure
cooled by SCCW
425°F = Trip
5 minutes unloaded = Auto Shutdown
Normally in Auto
5
component/position, cycle pressure, cycle off what? PS, cooled by what? temp trip? time unloaded, normally in what?
85-95# = SA-P-1B Cycles
power supply = 1D 480V TP MCC
cycle off receiver pressure
cooled by SCCW
425°F = Trip
5 minutes unloaded = Auto Shutdown
Normally in Auto
6
component/position, cycle pressure, cycle off what? PS? normally in what?
85-115# = IA-P-2A/B Cycles
power supplies = 1A/B ES MCC
cycle off receiver pressure
Normally in Auto
7
pressure, alarm
85# = IA low pressure alarm for Primary or Secondary Plant
8
component/position
pressure
PS
85# = IA-V-2104A/B open
power supply = 1Q DC
9
pressure
component/position
how does it reset?
80# = IA-V-1 opens
Auto Reset
10
pressure
alarm
75# = SA low pressure alarm
11
pressure
component/position
closed how and from where?
75# = IA-V-2133 opens
manually closed from CR
12
pressure
component/position (swap)
component/position (2 valves open/feed), 4 CO, 6 FW, 6 MS
70# = IA-P-2A/B switching valves swap
IA-V-1542/1533 open and feed
CO-V-5/7/8/51
FW-V-7A/B, 16A/B, 17A/B
MS-V-3A-F
13
pressure
manual action
60# = Trip Reactor (manual)
14
component/position
answer auto opens(resets)
PS
60# = IA-V-26 closes
auto opens (resets)
power supply = 1Q DC
15
pressure
component/position to do what
4 MS valves, 4 EF, 1 RR
60# = IA-V-1626A/B open to supply 2 HR Air to:
MS-V-4A/B, 6 & PC-5
EF-V-30A-D
RR-V-6
16
pressure
component/position action
all 2 HOUR air valves do what?
60# BANK PRESSURE = IA-V-1625A/B open and vent banks to atmosphere
all 2HR air valves FAIL SAFE