Section 3.6 CONTAINMENT Flashcards
What is T.S. 3.6.1 Containment?
Any 1 hour or less actions?
T.S. 3.6.1 Containment
Modes 1-4, Containment Shall be Operable
Containment inoperable, restore to operable within 1 hour.
What is T.S. 3.6.2 Containment Air Locks?
Any 1 hour or less actions?
Modes 1-4, Two Containment Air Locks shall be Operable.
A: One or more containment air locks with one containment air lock door inoperable. Verify the operable door is closed within 1-hour.
B: One or more containment air locks with containment air lock interlock
mechanism inoperable. Verify an operable door is closed in the
affected air lock within 1-hour.
One or more containment air locks inoperable for reasons other than
Condition A or B. Initiate action to evaluate overall containment leakage
rate per LCO 3.6.1. immediately and within 1 hour verify a door in the affected air lock is closed.
What is T.S. 3.6.3 Containment Isolation Valves?
Any 1 hour or less actions?
Modes 1-4, Each containment isolation valve shall be operable.
Penetration flow paths with two containment isolation valves and two inoperable isolation valves, isolate the affected flow path within 1-hour.
One or more purge exhaust or air room supply valves not locked closed, locked closed the affected valve within 1-hour.
What is T.S. 3.6.4 Containment Pressure?
Any 1 hour or less actions?
Modes 1-4, Containment pressure shall be ≤ 1.0 psig in MODES 1 and 2 and ≤ 1.5 psig in MODES 3 and 4.
Containment pressure not within limits, restore containment to within limits in 1-hour.
What is T.S. 3.6.5 Containment Air Temperature?
Any 1-hour or less actions?
Modes 1-4, Containment average air temperature shall be ≤ 140°F.
No 1-hour or less actions.
What is T.S. 3.6.6 Containment Cooling?
Any 1-hour or less actions?
Modes 1-3, Two containment cooling trains shall be OPERABLE.
Less than 100% of the required post accident containment cooling capability available. Enter LCO 3.0.3 immediately.
What is the minimum equipment that can be used to meet 100% containment cooling with MSIV bypass valves closed?
2 containment spray pumps and 2 spray headers OPERABLE
OR
1 containment spray pump
2 spray headers
3 safety related CACs, OPERABLE
(at least two service water pumps must be OPERABLE if CACs are to be relied upon).
What minimum equipment is needed to meet 100% containment cooling with the MSIV bypass valves open?
2 containment spray pumps
2 spray headers,
2 safety related CACs, are OPERABLE (at least two service water pumps
must be OPERABLE if CACs are to be relied upon)
OR
1 containment spray pump
1 spray header
3 safety related CACs are OPERABLE (at least three service water pumps must be OPERABLE to provide the necessary service water flow to assure OPERABILITY of the CACs).
Which SDC heat exchanger can have containment spray isolated and which can’t?
E-60A, SDC Heat Exchanger, has no isolation on the spray pump discharge line into the heat exchanger, E-60B, however, does.
If spray pump discharge, (tube side), of E-60B is isolated, what is required for 100% containment cooling?
3 Safety related Containment Air Coolers
2 Containment Spray Pumps
2 spray headers
2 CCW pumps (P-52A and P-52B)
2 SWS pumps, and both CCW Heat Exchangers,
and if
1 CCW Containment Isolation Valve, CV-0910, CV-0911, or
CV-0940, is OPERABLE
and
2 CCW isolation valves for the non-safety related loads outside
the containment, CV-0944A and CV-0944 (or CV-0977B), are
OPERABLE.
When do the CAC ‘A’ Fans get a start signal?
Only via the DBA sequencer. SIAS/CHP do not start them.