RHR Flashcards
What is the design flow for LPCI mode of RHR?
10,300gpm per pump @20psid RPV pressure
17,000gpm per loop @20psid RPV pressure
What are the suction sources for RHR?
Suppression Pool
Shutdown Cooling (RPV)
What are the permissives to open the F020 Torus Suction valves?
Both F006s SDC suction in the same loop must be full closed
What permissives are required to open the F006 SDC suction valves?
The F020 Torus suction AND the F028 Torus Isolation must be full closed in the same loop
WHat are the power supplies for each RHR pump?
3412
1(2)A - E3
1(2)B - E4
1(2)C - E1
1(2)D - E2
Which RHR pumps have alternate ASSD power supply?
Div 2 pumps
What will trip an RHR pump?
Loss of suction - F004 AND F006 OR F008 OR F009 not full open will energize no suction trip relay
Anti Pump coil prevents re-shutting breaker until closing signal is removed
*this trip is still active when RHR is in local control from RSDP*
What RHR valves are powered by the opposite unit?
F028A/B - Torus Isolation
(RCR) F031&F032A/B RCR discharge and bypass
F015A/B - Inboard injection
F017A/B Outboard injection
What is the purpose of the RHRSW booster pumps?
Maintain service water (tubes) >15psi higher than RHR (shell)
This prevents reactor coolant from leaking into the atlantic ocean via service water
What are the heat exchanger flow limits for RHR flow?
1 RHR pump - 4150-10000gpm
2 RHR pump - 8300-11500gpm
What are the heat exchanger flow limits for RHRSW flow?
1 RHRSW pump - 2000gpm to 4000gpm
2 RHRSW pumps - 5000 to 8000gpm
What is the normal service water supply for each loop of RHRSW?
Div 1 (A&C) - CSW
Div 2 (B&D) - NSW
can be cross connected
What will cause the RHR room coolers to start?
North RHR: 98dF in either RHR room or 120dF in HPCI room
South RHR 98dF in either RHR room or 145dF in HPCI room
North cooler has a fail to start alarm after 15seconds.
South cooler has no fail to start alarm
What is the effect of an inop RHR room cooler with regards to Tech Specs?
1 INOP cooler = 1 INOP loop of RHR (pick one)
2 INOP cooler = LCO 3.0.3 - inop both loops of LPCI and HPCI
When will the F007 RHR min flow valve open?
Auto opens when breaker closes for associated pump and flow <2230gpm for 10 seconds
Valve must be manually closed if open when pump is secured