HPCI Flashcards
What signals will auto initiate HPCI?
LL2 (105”)
OR
Hi DW pressure (1.7#)
What happens on a HPCI initiation?
- White initiation light
- F059 - cooling water valve - OPEN
- F004 - CST suction valve - OPEN
- F007 - pump discharge - OPEN
- F008 &; F011 - test return line - CLOSED
- Vacuum pump starts
- F001 - steam supply - OPEN
- F025/F026 - condenser drain - closed
- Aux Oil Pump starts
- V9 Governor valve initially strokes open then closed and the V8 turbine stop valve starts to open
What causes a Group 8 Isolation and what valves are affected?
LL 1 (166”)
OR
High steam dome pressure (131#)
RHR SDC suction valves F008, F009 close
RHR Inbd Injection Isolation F015 on LL1 only if F008 or F009 are not full close
What causes a Group 4 isolation?
SELF
- Steam line low pressure - 115#
- Exhaust Diaphragm Pressure - 7#
- Leak Detection
- HPCI equip area 165F
- HPCI steamline area 165F
- Tunnel deltaT 47F
- HPCI steam tunnel 165F, 190F
- Flow high (steam) - 220% for 5 seconds
- Manual (closes outboards only)
What is the normal suction source for HPCI?
CST
Where does HPCI inject?
Feedwater line A
What will cause HPCI to swap suction to alternate? What is the alternate supply?
Suppression Pool
Low CST level (<3’5”) OR hi torus level (-25”)
When does the HPCI min flow valve open?
<400gpm and >140#
closes >1400gpm
What causes a HPCI trip?
Manual Overspeed - 4600rpm Level - 206” Exhaust pressure high - 157.5# Suction pressure low - 15” vacuum for 13 seconds Any isolation signal
When do HPCI trips reset?
All except level and isolation clear when condition clears. high level seals in until LL2 or manually reset High DW pressure will NOT initiate HPCI if tripped on LL2
What are the group 4 valves?
HPCI steam F002 (inboard - Div 2 AC) F003 (outboard - Div 1 DC) HPCI Torus Suction F042 (inboard - div 1 DC) F041 (outboard - div 1 DC)
What are the group 7 valves?
HPCI Exhaust Vacuum Breakers F079 inboard - Div 2 AC F075 outboard - Div 1 AC
What are group 7 isolation signals?
Steam line low pressure (115#) ANDDrywell Press High (1.7#)
What is a HPCI turbine trip?
HPCI turbine trip solenoid energizes to trip V8
What are the effects of a loss of panel 3A(4A) on HPCI?
HPCI will not operate, outboard isolations fail to closeTorus suction valves fail open due to false CST low level signal