Raceways and Conductors Flashcards

1
Q

Where exposed to the weather, raceways shall be ___________?

A

Listed or approved for use in wet locations and arranged to drain.
225.22

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Most conduit and tubing type raceways have a maximum equivalent of four _______ bends between pull points.

A

quarter bends (90 degree)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

The cross-sectional area of 2-inch EMT is ________ inches squared.

A

3.14
A=3.14 x r^2 (in this case r = 2)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

All cut ends of conduits shall be reamed or otherwise finished to remove rough edges. Where conduit is threaded in the field, a standard cutting die with a ________-inch taper per feet (1 in 16) shall be used.

A

3/4 inch
342.28 and 344.28

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Multioutlet assemblies shall not be ?

A

installed in hoistways.
380.12

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Splices and taps shall be permitted within a wireway provided they are accessible. The conductors, including splices and taps, shall not fill the wireway to more than _____ of its area at that point.

A

75 %
376.56(A)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

A ______ is a metal transverse raceway for electric conductors, providing access to predetermined cells of a cellular concrete floor, thereby permitting the installation of electric conductors from a distribution center to the floor cells.

A

Header
372.2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

In both exposed and concealed locations, where a cable or raceway-type wiring method is installed through bored holes in joist, rafters, or wood members, holes shall be bored so that the edge of the hole is not less than _________ inches from the nearest edge of the wood member.

A

1 and 1/4 inch
300.4(A)(1)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

How many 14 AWG THHN conductors, including an equipment grounding conductor, can be installed in a 3/8 inch flexible metal conduit using inside fittings?

A

4
Table 348.22

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What is the maximum distance between supports for a straight run of 2 inch IMC made up with threaded couplings?

A

16 feet
342.30(B)(2) & Table 344.30(B)(2)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

The sum of cross-sectional areas of all contained conductors and cables at any cross section of a wireway shall not exceed _______ fill.

A

20%
376.22(A)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Where conductors carrying alternating current are installed in ferrous metal raceways, they shall be so arranged as to avoid heating the surrounding metal by __________?

A

Induction
300.20(A)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

A ____________ is a type of surface, flush, or freestanding raceway designed to hold conductors and receptacles, assembled in the field or at the factory.

A

Multioutlet Assembly
100

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Where practicable, contact between dissimilar metals anywhere in the system shall be avoided to eliminate the possibility of _____________.

A

Galvanic action
342.14

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

What is the maximum number of 4 AWG THHN conductors permitted in 1 1/2 inch rigid metal conduit?

A

10
Anniex C

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Where the same 4 AWG conductor enters and then exists a wireway through conduit or tubing, the distance between those raceway entries shall not be less than ________ times the trade diameter of the larger raceway.

A

6 times for Angle and pulls
314.28(A)(1)

8 times for straight pulls
314.28(A)(2)

17
Q

All components of an exposed wiring system, installed where walls are frequently washed, must be mounted with a minimum of ________ inch airspace between components and the wall.

A

1/4 inch
300.6(D)

18
Q
A