In pull boxes or junction boxes having any dimension over _______ feet. All conductors shall be cabled or racked up in an approved manner.

A

6ft (72in)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

A nonmetallic extension can be run in any direction from an existing outlet, but shall not be run on the floor or within ______ inches from the floor

A

2 inches
382.15(A)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Outlet boxes that do not enclose devices or utilization equipment shall have a minimum internal depth of ______ inches?

A

1/2 inch
314.24

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

In damp or wet locations, surface-type enclosures (within scope of Article 312) shall be so placed or equipped as to prevent moisture or water from entering and accumulating within the cabinet or cutout box and shall be mounted so there is at least _______ inch of airspace between the enclosure and the wall or other supporting surface.

A

1/4 Inch
312.2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

The minimum thickness in inches for a steel box measuring 6 in x 4 in x 3.5 in is ________ inches.

A

0.0625 Inches
314.40(B)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Covers of outlet boxes and conduit bodies having holes through which flexible cord pendants may pass shall be provided with approved ________ or shall have smooth, well-rounded surfaces on which the cord may bear.

A

Brushings
314.25(C)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Where permanent barriers are installed in a junction box, each section shall be considered as a _________.

A

Separate Box
314.28(D)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the maximum number of 12 AWG THW conductors permitted in a 4-inch octagon box that is 1.5 inches deep? (The box contains a fixture stud and a Hickey)

A

4
Table 314.16(a)
314.16(B)(3)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

A means must be provided in each metal box for the connection of a ______________.

A

Equipment ground conductor
314.40(D)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Installation in or behind a surface of concrete, tile, gypsum, plaster, or other non-combustible material, including boxes employing a flush-type cover or faceplate, shall be made so that the front edge of the box, plaster ring, extension ring, or listed extender will not be set back of the finished surface more than __________ inches.

A

1/4 inch
314.20

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

Nonmetallic boxes shall be suitable for the lowest __________ Conductor entering the box.

A

Temp Rated
314.17(C)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

An electrician needs to install a surface-mounted, nonmetallic, weatherproof cabinet on the outside of a concrete block building. Since the cabinet must be mounted in an wet location, it must be mounted so there is at least _________ inches of airspace between the cabinet and the wall.

A

0
312.2 Exception

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

How many 14 AWG THW conductors are permitted in a 3 in. x 2 in. x 2.5 in. device box?

A

6
Table 314.16(A)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Nonmetallic surface mounted extensions must be secured in place by approved means at intervals not exceeding ________ inches.

A

8 inches
382.30(A)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

A 2.5-in. rigid metal conduit enters the back of a pull box with a removeable cover on the opposite side. The raceway encloses four 4/0 AWG THHN copper conductors and one 4 AWG equipment grounding conductor. The minimum depth for this pull box is__________-?

A

4 inches
Table 312.6

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

Where nonmetallic boxes are used with open wiring or concealed knob-and-tube wiring, the conductors must enter the box through ___________.

A

Individual holes
314.17(C)

17
Q

Luminaires weighing no more than _______ pounds can be supported by boxes not specifically designed to support luminaires, provided the luminaire, or its supporting yoke, is secured to the box with at least two No. 6 or larger screws.

A

6 lbs.
314.29(1) Exception

18
Q

For straight pulls, the length of the box shall not be less than ________ the outside diameter over sheath, of the largest shielded conductor or cable entering the box on the systems over 1000 volts nominal.

A

48 Times
314.71(A)

19
Q

Approved drainage openings not smaller than _______ and not larger than ____ in diameter shall be permitted to be installed in the field in boxes or conduit bodies listed for use in damp or wet locations.

A

1/8 and 1/4
314.15

20
Q

unused openings, other than those intended for the operation of equipment, those intended for mounting purposes, or those permitted as part of the design for listed equipment, shall be closed to afford protection ________ to the wall of the equipment.

A

Substantially equipment
110.12 (A)