In pull boxes or junction boxes having any dimension over _______ feet. All conductors shall be cabled or racked up in an approved manner.
6ft (72in)
A nonmetallic extension can be run in any direction from an existing outlet, but shall not be run on the floor or within ______ inches from the floor
2 inches
382.15(A)
Outlet boxes that do not enclose devices or utilization equipment shall have a minimum internal depth of ______ inches?
1/2 inch
314.24
In damp or wet locations, surface-type enclosures (within scope of Article 312) shall be so placed or equipped as to prevent moisture or water from entering and accumulating within the cabinet or cutout box and shall be mounted so there is at least _______ inch of airspace between the enclosure and the wall or other supporting surface.
1/4 Inch
312.2
The minimum thickness in inches for a steel box measuring 6 in x 4 in x 3.5 in is ________ inches.
0.0625 Inches
314.40(B)
Covers of outlet boxes and conduit bodies having holes through which flexible cord pendants may pass shall be provided with approved ________ or shall have smooth, well-rounded surfaces on which the cord may bear.
Brushings
314.25(C)
Where permanent barriers are installed in a junction box, each section shall be considered as a _________.
Separate Box
314.28(D)
What is the maximum number of 12 AWG THW conductors permitted in a 4-inch octagon box that is 1.5 inches deep? (The box contains a fixture stud and a Hickey)
4
Table 314.16(a)
314.16(B)(3)
A means must be provided in each metal box for the connection of a ______________.
Equipment ground conductor
314.40(D)
Installation in or behind a surface of concrete, tile, gypsum, plaster, or other non-combustible material, including boxes employing a flush-type cover or faceplate, shall be made so that the front edge of the box, plaster ring, extension ring, or listed extender will not be set back of the finished surface more than __________ inches.
1/4 inch
314.20
Nonmetallic boxes shall be suitable for the lowest __________ Conductor entering the box.
Temp Rated
314.17(C)
An electrician needs to install a surface-mounted, nonmetallic, weatherproof cabinet on the outside of a concrete block building. Since the cabinet must be mounted in an wet location, it must be mounted so there is at least _________ inches of airspace between the cabinet and the wall.
0
312.2 Exception
How many 14 AWG THW conductors are permitted in a 3 in. x 2 in. x 2.5 in. device box?
6
Table 314.16(A)
Nonmetallic surface mounted extensions must be secured in place by approved means at intervals not exceeding ________ inches.
8 inches
382.30(A)
A 2.5-in. rigid metal conduit enters the back of a pull box with a removeable cover on the opposite side. The raceway encloses four 4/0 AWG THHN copper conductors and one 4 AWG equipment grounding conductor. The minimum depth for this pull box is__________-?
4 inches
Table 312.6