Cables Flashcards
Nonmetallic-sheathed cable must be secured within _________ inches from a two-gang plastic device box.
12 inches
334.30
Floor-mounted Type FCC cable, cable connectors, and insulating ends shall be covered with carpet squares no larger than __________ inches square.
39.37 in square (1.0 m square)
324.41
Type AC cable shall be secured by staples; cable ties listed, labeled, and identified for securement and support; straps, hangers, or similar fittings; or other approved means at intervals not exceeding ____________ feet.
4.5 feet
320.30(B)
The minimum bending radius for 3-inch diameter integrated gas-spacer cable is ________ inches.
35 inches
Table 326.24
________ is a factory assembly of one or more insulated circuit conductors with or without optical-fiber members enclosed in an armor of interlocking metal tape or a smooth or corrugated metallic sheath.
Metal-Clad Cable
330.2
Where type MI cable terminates, a seal shall be provided immediately after stripping to prevent the entrance of _______ into the insulation.
Moisture
332.40(B)
Where nonmetallic-sheathed cable is run at angles with joists in unfinished basements, it shall be permissible to secure cables not smaller than three _______ AWG conductors directly to the lower edges of the joints.
Two 6 AWG or Three 8 AWG
334.15(C)
________ is a single or multiconductor solid dielectric insulated cable rated 2001 volts or higher.
Medium-Voltage Cable (Type MV)
328.2
The overall covering of Type UF cable shall be _______.
Flame retardant, moisture, fungus and corrosion resistant; and suitable for direct burial in the earth.
340.116
Power feed, grounding connection, and shield system connection between the FCC system and other wiring systems shall be accomplished in a ________ identified for this use.
Transition assembly
324.40(D)
Type AC cable shall be permitted to be unsupported where the cable is not more than _________ inches in length at terminals where flexibility is necessary.
2 feet (24 inches)
320.30(D)
The _______ for the controlled lighting circuit shall be installed at the location where switches control lighting loads that are supplied by a grounded general-purpose branch branch circuit serving bathrooms, hallways, stairways, or rooms suitable for human habitation or occupancy as defined in the applicable building code.
Grounded Circuit Conductor
404.2(C)
The minimum bending radius for metal-clad cable is ________ times the external diameter of the metallic sheath.
10 times go up to 3/4
330.24(A)(1)
12 times for more than 3/4 but less than 1.5 inch
320.24(A)(2)
15 times for over 1.5 inch
320.24(A)(3)
In both exposed and concealed locations, where a cable or raceway-type wiring method is installed through bored holes in joists, rafters, or wood members, holes shall be bored so that the edge of the hole is not less than _________ inches from the nearest edge of the wood member.
1 1/4 inch
300.4(A)(1)
Attics with permanent stairs that have cables within _________ feet of the floor can run through the studs if meeting requirements 300.4(D). Cables more than _________ feet above the floor can run across the face of framing.
7 feet
320.23(A)