Qual, Fire Life Safety Flashcards

1
Q

Describe the standard pre-action system as it exists on campus to include:

A

Describe the standard pre-action system as it exists on campus to include:

Power Supplies – Dual fed. ATS (fed off the G pnl)

Water Flow Path – Water entry room (L151), PBB pipes, pre-action, suites

Valve Isolation Points – Water entry room and pre-actions

Alarming Set Points – Tamper, high/low pressure alarm (10 psi), Blast Off

Types of Fires and Proper Extinguishing Agents

A: General combustions (Ash)

B: Liquids (Boils)

C: Electrical (Charge)

D: Metals (Drill)

K: Kitchen/Grease (Kitchen)

Maintenace Scope of Work

Simulate air loss, check switches, and close isolation valves

Maintenance Periodicity

Quarterly: Test tampers and bring in low supervisory

Annually: Cycle deluge valve, alongside quarterly testing

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the difference between cross zone and cross detection?

A

Cross Zone (underfloor): HSO Activation. Prevents false alarms. Smoke in different zones needed.

Cross Detection (ceiling): Requires 2 with same zone and pressure loss (2 factor authentication) dual interlock.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Describe the underfloor smoke detection disabling procedure. How does this differ between properties?

A

Call BFPE (T/S), disarm HSO by turning key, acknowledge the supervisory alarm.

Different buildings have different building codes and some don’t have HSO’s.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Where is the Life Safety Building Account and Passcode spreadsheet published?

A

I: Drive – Fire Folder

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Describe the Fire System response to 2 underfloor cross zoned smoke detectors.

A

HSO relay is activated (shut trip) and breakers in electric room will all trip, CRAC’s will all shut down/off HVAC s/d override goes off.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What indications would be available to the roving Facility Engineer with one ceiling smoke head activated within a suite?

A

BMS alarm, light on panel will light up for location of ceiling smoke head, alarm on fire panel in suite, alarm will sound off.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What should be observed prior to placing a Suite HSO inhibit key switch from inhibit to enable?

A

All work is complete, no alarm indications, all is normal

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Explain how the Very Early Smoke Detection Apparatus works and where on campus is this located?

A

M Building

VESDA: Sucks in air from the protected environment via purpose built aspirating pipe and fitting also samples the quantity of air passing through the VESDA detection laser chamber.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Explain the differences between Trouble/Supervisory/Alarms.

A

Trouble: system/component issue

Supervisory: Change of state in system

Alarm: Sensor triggered

How well did you know this?
1
Not at all
2
3
4
5
Perfectly