Generator System Flashcards
Describe the generator system in detail to include the following:
66 generators for building; 16 cylinders in each generator; no spark plugs, heater core. 4-pole generator
Basic component identification
Fuel System, Alternator, Engine, Battery Charger, Control Panel, Coolant System, Oil System
Internal Combustion Engine
Four Stroke – Intake, Compression, Combustion, Exhaust
C175
16 cylinder
84.8L
Generator running parameters
Ozone Season: (7am-5pm) May – September
Exceptions: Testing after Installation, Emergency, Maintenance
1800 RPMs = 480V/277V
180 degrees coolant temp
100 PSI fuel
Maintenance requirements
Monthly unloaded runs
Quarterly loaded runs
Semi-annual inspections
Yearly filter change
Maintenance Scope of Work
Oil Change, Filter Change, Check Coolant/Oil Levels
Alarming Set Points
Overspeed = 1860 RPM
Low Oil psi = 30 psi
Fuel – 72 psi
Over temp = 220 degrees
What actions will a Facility Engineer take if the suite goes on generator?
Engineer will be sent down by the lead to the effected electrical room to confirm the breaker closed for the generator and the utility opened and is supplying proper voltage. Check generator and take logs every 15 minutes. Report fuel rates and figure how long the generator can run and investigate the cause of the generator starting. Record the time and what has been done as well as the affected suite.
How many gallons of fuel do we maintain in each generator at full capacity? What percentage of the overall above ground storage tank capacity do we maintain in each tank? If asked for a thumb rule, approximately how many gallons of fuel are there in each inch of fuel in an average AST on campus?
House Gen 1 – 1,000 gallons
House Gen 2 – 2,000 gallons
Most - 5,900 gallons
155 gallons per inch
Customer Red – 10,900 gallons
272 gallons per inch
90%
Describe the importance of the generator enclosure dampers. What immediate actions are necessary if they fail to open during a generator load test?
Airflow, prevent overheating
Open the doors if you are able, if not, monitor closely and secure if necessary
Dampers fail open so if they don’t open it’s possible to manually open them.
Describe the operation of the Veeder Root system, to include the following:
What type of detector is used to determine fuel level?
Float Sensor
Probe sensor
Ullage required within our generator tanks
10% for expansion
(Fuel guys) Fosters – call around 60%
150 gallons per inch