P's, C's, & T's Flashcards
P-4
Rx Trip Permissive
Rx Trip and Bypass Breakers Open
- Trips Main Turbine
- FWIS w/ Low Tavg (564°F)
- Prevents re-actuation of SI after Reset
- Transfers CSDs from Load Reject to Plant Trip
- Arms Steam Dumps
P-6
Source Range Permissive
IR > 10-10 Amps (1/2)
- Permits Block of SR Trip
P-7
At-Power Permissive
P-10 or P-13 (1/2)
- Unblocks the following trips:
- PZR High Level
- PZR Low Pressure
- Low Flow in > 1 Loop
- RCP UV
- RCP UF
P-8
3 Loop Flow Permissive
PR > 48% (2/4)
- Unblocks Low Flow in 1 Loop Trip
P-9
Turbine Trip - Rx Trip
PR > 50% (2/4)
- Unblocks Rx Trip on Turbine Trip
P-10
Nuclear at Power
PR > 10% (2/4)
- Feeds P-7
- Blocks SR HV
- Permits Block of:
- IR Trip
- IR Rod Stop
- PR Low Setpoint Trip
P-11
Pressure SI
< 1970 psig (2/3)
- Permits block of:
- Low Pressure SI
- Low Steam Pressure SI/SLIS
- Enables SLIS on Hi Negative Pstm Rate
P-12
Low-Low Tavg
550°F (2/4)
- Blocks steam dumps (CSDs)
P-13
Turbine at Power
Pimp > 10% (1/2)
- Feeds P-7
P-14
S/G High Level
SG Level > 91% (2/4 LTs on 1/4 S/Gs)
- Trips MFPs
- Trips Main Turbine
- FWIS
All Rx Trips
- Trips
- Setpoints
- Coincidence/Interlocks
- Protection
C-1
IR Rod Stop
20% PR Equivalent (IR Amps) - 1/2 IR channels
- Stops outward rod motion
C-2
PR Rod Stop
103% - 1/4 PR (Can Be Bypassed)
- Stops outward rod motion
C-3
OTΔT Rod Stop & Runback
OTΔT Trip - 2%: 2/4
- Stops outward rod motion & causes turbine runback
C-4
OPΔT Rod Stop & Runback
OPΔT Trip - 2% on 2/4
- Stops outward rod motion and causes turbine runback
C-5
Low Power Interlock
15% Power by Pimp
- Auto Rod Withdrawal disabled.
C-7
Loss of Load
10% Step or 5%/min decrease in Pimp
- Manually Reset (PT-506 Only)
- Arms steam dumps in Tave Mode
C-9
Condenser Interlock
Cond. Pressure < 6.0” HgA (2/2 per shell, there is one C-9 for each condenser)
- Condenser available for CSDs.
C-11
Control Bank ‘D’ Rod Withdrawal Limit
223 Steps
- Auto Rod Withdrawal disabled
C-20
AMSAC
Pimp > 40% on 2/2 (505 & 506)
- Arms AMSAC