NB Bus Feeder Breakers (NB0112, 0212, 0209, 0109)
- Requirements to close
- Trips
A
- To close manual from MCB:
- Synch Scope ON
- No faults on breaker or Xfmr
- Alt (Normal) and AEPs Breakers OPEN
- Synch Check lit (if paralleling w/ EDG
- Trips:
- Manual
- Bus UV
- Xfmr Fault
- Feeder Breaker Fault
2
Q
Stopping an AEPs Diesel
A
- Stop Push Buttons:
- On respective breaker cubicle on PA501 (Switch House)
- Outside door on DG Enclosure
- Inside enclosure on enging control panel
- Inside enclosure mounted one engine
3
Q
Methods to Start EDG
A
- Manual @ MCB via Start/Reset PB (Master Xfer Switch in AUTO)
- Manual @ Local Generator Control Panel via Start PB (Master Xfer Switch in LOC/MANUAL)
- Manual by actuation of either air start solenoid
- **Manual via Local Generator Control Panel via Popout Button
- **Auto - NB Bus UV (2/4) via LSELS (Master Xfer Switch in AUTO)
- **Auto - SIS via SSPS (Master Xfer Switch in AUTO)
** Emergency Starts: Operator Voltage/Frequency controls disabled until unit parallel switch momentarily placed in parallel, signal is reset, and Start/Reset PB pressed.
4
Q
EDG Local Emergency Start
- List the methods & order of preferance for a local emergency start of the DGs per the EOPs
A
- Reset Engine Shutdown Relay or Stat Failure Relay by pressing Engine Shutdown Reset PB
- Emergency Start Popout button on Generator Control Panel (Break Glass or remove glass cover).
- Place Master Transfer Switch in LOC/MANUAL then press START
- Manually actuate either air start solenoid.
5
Q
NK Batteries
- Ratings of each battery
- T/S requirements for DC Sources
A
- NK11 & 14: 1650 Amps/hour
- NK12 & 13: 900 Amps/hour
- All are rated to supply emergency loads for 200 minutes without chargers.
- Train:
- NK01 powered from NK11 and NK21 or NK25 (swing) powered from NG01 (PG19 not acceptable)
- Same for NK03 to constitute Train A.
- ** NK25 may only be credited once.
- T/S 3.8.4/5:
- Modes 1-4: 2 Trains
- Modes 5-6 and during irradiated fuel movement: 1 train
6
Q
XNB01/02 Trips
A
[NFLGOD]
- Neutral Ground OC
- Fault - Transformer (2/2)
- Low Oil Level (Xfmr Low-Low Level & LTC “Critical Low”)
- Ground Overcurrent
- Overcurrent
- Differential Overcurrent
7
Q
NG Bus Tie Breakers (NG0116 & 0216)
- Interlocks when racked out
- T/S Implications
- Limitations on Cross-Connecting
A
- If tie breakers are racked out, the associated supply cannot be closed (NG0101 and NG0201 respectively)
- When NG busses are x-tied all four DEGRADED bus voltage channels for their respective NB bus are INOPERABLE per T/S 3.8.9
- T/S Action 3.3.5.B.1
- T/S Action 3.8.1.F
- DO NOT EXCEED 1200 Amps on bus from feeding both NG busses from 1 NG Xfrm.
8
Q
S/U Xfmr
- Manual Closing
- Auto Close features
A
-
Manual:
- Local: Racked in and Local HS in Close
- MCB: HIS-6 in closed, source Synch Scope in SUT, S/U Xfmr engergized, Synch Check relay Sat, No LOs on SUT, No LOs on SUT or UAT output breakers.
-
Auto Fast Xfer:
- HIS-6 in Normal after Trip; V53 and V55 open, or MA Fault, or MD fault; S/U Xfmr energized; Synch Relay energized; No LOs on SUT; No LOs on SUT or UAT Breakers.
-
Auto Dead Bus Xfer:
- HIS-6 in Normal after trip; V53 and V55 open, or MA Fault, or MD Fault; 10 cycle TD after UV; UAT output breaker open; No LOs on SUT; No LOs on SUT or UAT Breakers.
9
Q
S/U Xfmr Trips
A
- Bus Feeder (PA0110, PA0202) Lockouts (LOs)
- SUT LO (High Side)
- SUT LO (Low Side)
- UAT Breaker selected and closed
10
Q
PB03/04 Feeder Bus (PB0306/PB0402)
- Closing Operation
- Trips
PB03/PB04 X-Tie Breaker (PB0401)
- Manual Operation
- Auto Operation
A
PB0306/PB0402
- Manual Operation from Local or MCB
- Trips on:
- Xfmr OC
- Ground OC
- Neutral Ground OC
- Differential OC
- Transformer Overpressure (2/2)
PB0401
- Closed from MCB If:
- Synch Check SAT
- NO Breaker Faults
- NO Faults on PB03 or PB04
- Auto close if:
- XPB03 or XPB04 LOs and control switch is Normal
- Auto Trip if:
- Bus tie ground fault → also trips bus feeders
- Bus feeder breaker fault
11
Q
PG Load Center Feeders
- Trips
- PG Tie Breaker Interlocks
A
- Trips:
- Manual
- OC
- Respective 13.8kV Feeder Breaker (PA0105, 0106, 0207, 0206) trips on fault
- If Xfmr LO it will trip its 13.8kV feeder and all Load Center Supply Breakers
- Tie Breakers
- If tie breaker racked out the following supply breakers cannot be closed:
- PG1101, 1301, 1601, and 1901.
- PG1201, 1401, 1501, and 2001 can be closed.
- If tie breaker racked out the following supply breakers cannot be closed:
12
Q
PJ and PK
- PJ Loads
- Chargers & ratings (PJ & PK)
A
PJ
- S/G Feedwater Pump Emergency LO Pump (2)
- Generator Emergency LO Pump
- Generator Emergency Seal Oil Pump
- PG12 → PJ21
- NG02 → PG31
- 200 Amps/hour chargers
- PJ11 Rated for 1200 Amps/hr for 120 minutes
PK
- NG01 → PK21/23
- NG04 → PK22/24
- 300 Amp/hour chargers
- PK Batteries 2400 Amps/hour for 120 minutes
13
Q
UV and Degraded Voltage
- List setpoints, coincidences, and logic for:
- UV (NB Bus)
- Degraded Voltage
A
-
UV:
- __70% voltage
- 2/4 detectors
- 1 second
-
Degraded Voltage
- 90% voltage for 8 seconds
- 2/4 detectors
- Causes trip after 111 time delay w/o SI Signal.
- Immediate Trip with SI Signal (After 8 seconds)
14
Q
SDS and LOCS Sequencer
- Inputs to SDS and LOCA Sequencer
- How to reset each sequencer
A
-
SDS
- __Inputs:
- Normal & Alternate Breaker Positions
- DG Breaker Positions
- No CSAS or SI Signal
- Reset:
- Off-site power restored to bus
- Normal or Alternate Feeder Breaker Closed
- __Inputs:
-
LOCA
- __Inputs:
- SSPS Cabinets (SI, CSAS) and UV Signals
- DG Output Breaker position and CSAS or SI
- Reset:
- SIS Reset PBs on RL002 and/or
- CSAS reset PBs on RL018
- __Inputs:
15
Q
PN11/PN12
- Power Supplies
- What they provide
- Backups
A
- Supplies DFWCS
- DC (1st Alt) supplies if normal supply lost.
- 2nd Alt supplies via static transfer and bypass switch if Inverter fails.
- When supplied by PK Batteres, UPS will shutdown and secure DFWCS after 60 minutes.