According to RCNY 907-01, it is unlawful to transmit two or more unnecessary alarms in any period of ____________.
three months
Manual pull station needs to be _____ above ground
4 feet
A certificate of of Fitness holder, after observing smoke detectors which appear to be painted shall __________________________________.
make a log and notify the building owner that the smoke detectors need to be replaced.
___________________ can be used in fire alarm systems.
Sealed lead acid batteries
By NYC fire code definition, an unnecessary alarm is considered to be an alarm ________________________.
caused by a cigarette smoke from a lit cigarette in a non-smoking area.
Smoke detectors with a reading of ______ outside of the manufactures recommended shall be replaced.
0.25
A smoke detector maintenance log book must be readily accessible on premises for a period of ___________ from the original entry.
3 years
Based on the 1968 building code, a coded alarm signal shall consist of not less than _____ of the number transmitted. Each number shall consist of ______.
four rounds; three impulses
Skyscraper is a Class
A
___________________ shall be responsible for ensuring that the fire and life safety systems are maintained in good working order at all times.
The building owner
__________________ can be used in fire alarm systems.
Sealed lead acid batteries
Crossed zone circuits are utilized especially where detectors _________________.
initiate a discharge of an extinguishing system
A central station log book should be kept for a minimum of ________ from the original entry.
6 years
__________________ should not patrol more than _________________ of building floor area.
Fire Guards; 50,000 square feet
The minimum distance between a smoke detector and an air supply should be _________
3 Feet