_______ is the color classification for heat detector rated at _______.
Blue; 275F
________ is the minimum listed minimum spacing for a combination smoke/heat detector.
50 feet
What is the minimum listed spacing for a combination smoke/heat detector?
50 feet
The maximum number of supervisory signal-initiating devices permitted to be connected to a single initiating device circuit shall be ________.
20
The maximum number of water-flow switches that can be connected to a initiating device circuit is ____.
5
How many smoke detectors are required for a room with a level ceiling of a 900 square feet or less?
1
Visual notification appliances on a fire alarm system shall not be located more than __________ from the end of the corridor.
15 feet
Flame detectors are suitable for use in _____________________.
high ceiling open spaced buildings
When connecting visual notification appliances on a fire alarm system, the flash rate shall not exceed ____________.
two flashes per second
A fire alarm control panel shall recharge batteries within _________ after fully charged batteries have been subject to a single discharge.
48 hours
At minimum, how long shall a supervising station maintain records on signals received from maintenance, inspections and testing?
36 months
The temperature classification a heat-sensing fire detector with a green color code means __________.
very extra high
The total sound pressure level produced by combining the ambient sound pressure level with all audible notification appliances operating in the occupied area shall not exceed ______.
110db
The maximum allowable response delay on an alarm signal from an initiating device shall receipt by the control unit shall be _________.
10 Seconds
An engine driven generator for public fire alarm reporting system __________.
Shall be tested weekly
A speaker is tapped at 1/4 watt and produces a sound level of 75db, if the speaker is tapped the 1 watt will produce _____.
81db
A fire alarm system in which components are used in whole or in part, in common with a non-fire signaling system.
A combination system
For all other water tanks a signal shall be initiated when the water level falls or rises _______.
12 inches
Required signals shall not be lost, interrupted or delayed by more than ________ as a result of the primary power failure.
10 seconds
Fire alarm system providing general emergency voice alarm communication must provide for _________ hours of stand by power followed by ___________ minutes of alarm.
24; 15
_______ smoke detector is required for a room with a level ceiling of 900 sq. ft. or less.
One
Pressure tank signal shall be initiated when the water level falls or rises ______ inches.
three
Fire alarm systems providing general evacuation need to provide ________ of standby power, followed by a _________ of alarm power.
24 hours; 15 minutes