Electrical Code Flashcards
Article _______ of the National Electrical Code addresses the requirements for fire-stopping.
300 (NFPA 70 article 300.21)
______ AWG is the stranded wire allowed to be used in NYC fire alarm installations.
8
______ AWG is the minimum required wire for grounding a fire alarm system in NYC.
8
____________ of the national electrical code addresses the requirements for fire alarm.
Article 760
The requirements for grounding a fire alarm system are based on ____________________.
NYC electrical code Article 250.
The wire nuts used in NYC to splice fire alarm conductors must be rated at a temperature of _______.
150c
A notification appliance is located at the end of a 24V circuit. The device requires at least 24 volts in order to operate. ______ gage size wires are needed for this device to operate. (NFPA 20)
14
Supervisory operation for _______ followed by full load operation for _______ for systems with voice communications capability.
24 hours;6 hours
Supervisory operation for ______ followed by full load operation for ___________ for systems without voice communications capability.
24 Hours;15 minutes