Central Stations Flashcards

1
Q

Low power radio transmitters shall automatically repeat alarm transmission at intervals not exceeding __________ until the initiating device is returned to its non-alarm condition.

A

60 seconds

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

The central station shall dispatch personnel to arrive within ______ if protected premises equipment needs to be manually reset after testing.

A

2 hours

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Upon recite of trouble signal pertaining solely to matters of equipment maintenance of the fire alarm system, the proprietary supervising station operator shall initiate action to perform the following: ______________________________________________________________.

A

Dispatch personnel to arrive within four (4) hours to initiate maintenance if necessary. Notify the AHJ when interruption of service exists for four (8) hours or more.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

In the event of loss of primary lighting for a proprietary supervising station the emergency light shall operate for not less than ________.

A

26 Hours

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

A failure of a dact to transmit an alarm shall not prevent subsequent attempts, __________________________.

A

up to a minimum of 5 and a maximum of 10 have been attempted

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

If either transmission channel for a DACT fails, a trouble signals shall be sent within ____________.

A

240 seconds / 4 Minutes

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

A DACT shall be configured to seize the phone lines by __________________.

A

disconnecting the outgoing and incoming calls by off hook

How well did you know this?
1
Not at all
2
3
4
5
Perfectly