Maintenance - Test method Flashcards
A digital alarm radio receiver shall be visually inspected at least _________.
semi-annually
Smoke detectors found to have a sensitivity outside the listed and marked sensitivity shall be __________________________.
cleaned, recalibrate or be replaced
Supervised alarm notification appliances shall be visually inspected at least ________.
semi-annually
Sensitivity check on a smoke detectors is required _____________.
within one year of installation
After the first initial or re acceptance inspection, lead acid or dry cell batteries shall be inspected _________.
monthly
Supervised alarm notification appliances shall be visually inspected at least.
semi-annual
A DACT is required to be tested ____________.
annually
Regarding testing of the releasing system, ______________________________________.
testing personnel shall be cognizant of the hazards associated with inadvertent system discharge.
When changes are made to site specific software of a fire alarm system _____ of initiating devices that are not directly affected by the change and a maximum of ______ shall be tested so that the correct system operation will be verified.
10%; 50
A duct detector is required to be visually inspected _________.
Semi-annual
After the first initial or reactance inspection, nickel-cadmium or sealed lead-acid batteries should be visually inspected ___________.
Semi-annually
The fire alarm system transmitters shall be visually inspected at least _________.
semi-annually
Flame detector and spark/ember detector testing shall be performed with a _____________
Calibrated test method
After the first initial or reactance inspection, nickel-cadmium and sealed acid batteries shall be inspected
Semi-annually
A DACT is required to be visually inspected ________________.
semi-annually
A minimum of _______ detectors shall be tested on each initiating conventional device circuits.
two
A _______________ does not insure that each smoke detector is within its listed and marked sensitivity range.
A smoke entrance method
__________________________________, this statement is concerning the maintenance, testing and inspection records on a fire alarm system.
Software based systems require a generic copy of the software be provided to the owner,
When cleaning a smoke detector you should first, ____________________.
read the manufactures cleaning procedures.
___________________________ prior to testing and cleaning the smoke detectors.
Place the fire alarm system on test with the monitoring central station
When performing a load test on a standby battery it is necessary to ______________.
test with battery charger disconnected
The proper method to measure the voltage across battery terminals when performing a lead battery charger test is to _____________________.
leave the battery connected to the charger circuit
________________________________ is an acceptable method used to in testing smoke detector sensitivity.
A fire alarm control panel listed for the smoke detector sensitivity
The first functionality test of a smoke detector shall be performed _______________.
within one year of installation
When testing a radio alarm transmitter (RAT) ___________________________.
a fault between elements of the transmitting equipment shall be caused.
The proper way of testing a water-flow switch is to _____________________.
run water through the inspectors test valve
A digital alarm radio receiver shall be visually inspected at least ____________.
semi-annual.
Sensitivity check on a smoke detector shall be checked within _______ after installation.
1 year
A projected beam type detector shall be tested by introducing ______________.
an optical filter into the beam path.
Supervised alarm notification appliances shall be visually inspected at least.
semi-annual