A digital alarm radio receiver shall be visually inspected at least _________.

A

semi-annually

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Smoke detectors found to have a sensitivity outside the listed and marked sensitivity shall be __________________________.

A

cleaned, recalibrate or be replaced

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Supervised alarm notification appliances shall be visually inspected at least ________.

A

semi-annually

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Sensitivity check on a smoke detectors is required _____________.

A

within one year of installation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

After the first initial or re acceptance inspection, lead acid or dry cell batteries shall be inspected _________.

A

monthly

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Supervised alarm notification appliances shall be visually inspected at least.

A

semi-annual

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

A DACT is required to be tested ____________.

A

annually

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Regarding testing of the releasing system, ______________________________________.

A

testing personnel shall be cognizant of the hazards associated with inadvertent system discharge.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

When changes are made to site specific software of a fire alarm system _____ of initiating devices that are not directly affected by the change and a maximum of ______ shall be tested so that the correct system operation will be verified.

A

10%; 50

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

A duct detector is required to be visually inspected _________.

A

Semi-annual

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

After the first initial or reactance inspection, nickel-cadmium or sealed lead-acid batteries should be visually inspected ___________.

A

Semi-annually

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

The fire alarm system transmitters shall be visually inspected at least _________.

A

semi-annually

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Flame detector and spark/ember detector testing shall be performed with a _____________

A

Calibrated test method

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

After the first initial or reactance inspection, nickel-cadmium and sealed acid batteries shall be inspected

A

Semi-annually

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

A DACT is required to be visually inspected ________________.

A

semi-annually

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

A minimum of _______ detectors shall be tested on each initiating conventional device circuits.

A

two

17
Q

A _______________ does not insure that each smoke detector is within its listed and marked sensitivity range.

A

A smoke entrance method

18
Q

__________________________________, this statement is concerning the maintenance, testing and inspection records on a fire alarm system.

A

Software based systems require a generic copy of the software be provided to the owner,

19
Q

When cleaning a smoke detector you should first, ____________________.

A

read the manufactures cleaning procedures.

20
Q

___________________________ prior to testing and cleaning the smoke detectors.

A

Place the fire alarm system on test with the monitoring central station

21
Q

When performing a load test on a standby battery it is necessary to ______________.

A

test with battery charger disconnected

22
Q

The proper method to measure the voltage across battery terminals when performing a lead battery charger test is to _____________________.

A

leave the battery connected to the charger circuit

23
Q

________________________________ is an acceptable method used to in testing smoke detector sensitivity.

A

A fire alarm control panel listed for the smoke detector sensitivity

24
Q

The first functionality test of a smoke detector shall be performed _______________.

A

within one year of installation

25
Q

When testing a radio alarm transmitter (RAT) ___________________________.

A

a fault between elements of the transmitting equipment shall be caused.

26
Q

The proper way of testing a water-flow switch is to _____________________.

A

run water through the inspectors test valve

27
Q

A digital alarm radio receiver shall be visually inspected at least ____________.

A

semi-annual.

28
Q

Sensitivity check on a smoke detector shall be checked within _______ after installation.

A

1 year

29
Q

A projected beam type detector shall be tested by introducing ______________.

A

an optical filter into the beam path.

30
Q

Supervised alarm notification appliances shall be visually inspected at least.

A

semi-annual