Motors and Starters Flashcards

1
Q

The starting current using a DOL starter is the same as the running current, True or False?

A

False, it can be several times greater.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

According to the WA Distribution Connection Manual, a 4KW three phase squirrel cage motor has what maximum inrush current per KW?

A

8.6A per KW

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

The contactor of a DOL starter energizes when the start button is pressed but drops out when the start button is opened. Why might this happen?

A

A non-latching contactor has been installed, or the holding contacts are faulty.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What is the purpose of a Wye-Delta starter?

A

To limit the inrush current

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Describe the operation of a Wye-Delta starter?

A

When energized, the three phase motor is started while connected in Wye connection. Then after a set period of time, changes to run in a Delta connection.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

What is torque proportional to the square of?

A

Voltage

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Torque in a Wye connection is what percentage compared to a Delta connection?

A

33%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Voltage in a Wye connection is what percentage compared to a Delta connection?

A

57.5%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly