Motors and Starters Flashcards
The starting current using a DOL starter is the same as the running current, True or False?
False, it can be several times greater.
According to the WA Distribution Connection Manual, a 4KW three phase squirrel cage motor has what maximum inrush current per KW?
8.6A per KW
The contactor of a DOL starter energizes when the start button is pressed but drops out when the start button is opened. Why might this happen?
A non-latching contactor has been installed, or the holding contacts are faulty.
What is the purpose of a Wye-Delta starter?
To limit the inrush current
Describe the operation of a Wye-Delta starter?
When energized, the three phase motor is started while connected in Wye connection. Then after a set period of time, changes to run in a Delta connection.
What is torque proportional to the square of?
Voltage
Torque in a Wye connection is what percentage compared to a Delta connection?
33%
Voltage in a Wye connection is what percentage compared to a Delta connection?
57.5%