Any point in an electrical installation must not exceed what value of voltage drop from it’s nominal supply voltage?
5%
What is nominal voltage in a low voltage system in Australia?
230/400V 10% to -6%
What is nominal voltage in a low voltage system in Australia?
230/400V 10% to -6%
What is the Point of Supply in an underground service?
Service pillar (green dome)
What is the Point of Supply in an aerial service?
Mains connection box
What parts of an electrical service and installation is the electrician responsible for?
From the consumer side of the POS to the installation, and within the installation
Which tables of the AS/NZS 3008 are used to calculate voltage drop?
T40-42
When caculating voltage drop, Vc values are given in ______ phase.
Three phase
When calculating voltage drop, you must convert VC from _______ phase to _______ phase.
Three phase to single phase
The current value used to calculate voltage drop in a circuit may be defined by any one of which factors?
1 - Total of the connected load supplied through the circuit; or
2 - Maximum demand of the circuit; or
3- Current rating of the circuit protective device.
50% of the current rating of the protective device (ie circuit breaker) may be used for calculating voltage drop for which type of circuit
Final sub-circuit with distributed load (ie GPOs and lights)
When selecting cable based on a voltage drop calculation, you must choose a cable that has a Vc (greater than, less than) the calculated value.
Less than