Capstone - Testing & Verification Flashcards

1
Q

Before conducting testing on an electrical installation, what must you do?

A

A visual inspection

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Put the following in the order they would be performed during testing:

1- Sub-mains polarity test
2- Verify RCD operation
3- IR test of installation
4- Consumer mains polarity test
5- Final sub-circuit test for polarity and connections
6- Earth resistance test for continuity of main earth conductor
7- Earth fault-loop impedance test
8- Earth resistance test for earthed and equipotentially bonded parts

A

6
8
3
4
1
5
7
2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What are the four steps to isolate and test for de-energised?

A

1 - Test if switchboard is energised.
2 - Turn off CBs, isolate mains, LOTO.
3 - Test for de-energised on all circuits. Test meter after to prove it still works.
4 - Disconnect main neutral at POS. Disconnect main neutral at neutral bar. Disconnect MEN.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

What are the four steps to check for earth continuity?

A

1 - Disconnect possible parallel paths to earth (Hot Water systems). Prepare meter - zero out and test against 0.5 ohm and 1 ohm resistors.
2 - Test continuity to main earth with max of 0.5 ohm. Test continuity between electrode to clamp, clamp to main conductor.
3 - Test continuity of earth to equipotential bonds from earth bar with max of 0.5 ohm.
4 - Test continuity of earth bar to protective earths, max value per table 8.2.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

What are the four steps to perform Insulation Resistance testing?

A

1 - Disconnect meter neutral and functional earths. Zero meter and check operation against a 1MΩ resistor.
2 - Test consumer mains.
3 - Test sub-mains.
4 - Test final subcircuits.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

When doing IR testing on a circuit, what combinations of tests should be done?

A

Active to earth
Neutral to earth
Active to neutral

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

What is the minimum acceptable value when measuring IR during testing?

A

1MΩ

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What setting do you use on an IR tester while doing testing?

A

500VDC +20% -10%

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

What setting would you use on an IR tester during testing if there are electronics in the circuit which cannot be disconnected?

A

250VDC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

What are the five steps when doing polarity testing?

A

1 - Check continuity using ohmmeter or IR tester at 500 ohm setting. 10 & 5 ohm resistors. 10 ohm goes on active, 5 on neutral, both to earth.
2 - Continuity check across CB both on and off.
3 - Test for interconnections between circuit with other circuits and neutral bar.
4 - Test fault loop impedance

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

How do you test RCD function when de-energised?

A

Continuity checks across all poles of the device.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Where in the AS/NZS 3000 can you find a checklist to guide you for a visual inspection?

A

Clause 8.2.2 Pages 417-419

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

When testing socket outlets resistance value, you only need to check one socket of a double GPO True or False?

A

False, you must check both sockets of each double GPO.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

When testing Insulation Resistance testing on an extra-low voltage circuit, what setting would you use and what is the minimum IR value?

A

250VDC, 0.5MΩ

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

When testing Insulation Resistance on low-voltage circuits up to 500V, what setting would you use and what is the minimum IR value?

A

500VDC, 1MΩ

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

When testing Insulation Resistance on circuits above 500V, what setting would you use and what is the minimum IR value?

A

1000VDC, 1MΩ

17
Q

The functional earth of an RCD shall not be (less than, greater than) what value, on an IR tester?

A

0.05MΩ

18
Q

Table 8.1 is used when doing a fault-loop impedance test on a circuit that is energised or de-energised?

A

Energised.

19
Q

Table 8.2 is used when doing fault-loop impedance test on a circuit that is energised or de-energised?

A

De-energised.