Capstone - Oral Questions Flashcards

1
Q

Other than a hot water system, which equipment should have an equipotential bond?

A

Any metallic parts of equipment that house or otherwise may come into contact with exposed live parts or conductors.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What is the minimum size MEN link when the consumer mains are not protected? What AS 3000 clause?

A

Rated for at least the current carrying capacity of the main neutral conductor. 5.3.5.2

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Show / Name parts of earthing in the capstone electrical installation.

A

1 - Earth electrode
2 - Main earth conductor
3 - Main earth bar
4 - MEN link
5 - Protective earth conductors
6 - Equipotential bonds

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How far from the floor are you permitted to install a main switch? Which AS 3000 clause?

A

2m.
2.3.3.3

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Is it permissible to switch or isolate an earthing conductor? Which AS 3000 clause?

A

No.
2.3.2.1(c)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Is it required to identify the neutrals of circuits in a switchboard? Which AS 3000 clause?

A

Yes.
2.9.5.4

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Is it permissible to connect a 2.5mm neutral to the load side of an RCD?

A

Yes, if it’s the only neutral conductor in the RCD.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the minimum required conductor size for an underground single phase consumer mains, in WA?

A

10mm.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Describe the connection and purpose of the MEN link.

A

Connect the main neutral and main earth at the (main) switchboard. Allows the main neutral to carry any active to earth fault current.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

In a domestic switchboard, are all circuit protection devices required to operate in the same direction?

A

Yes.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

If no earth link exists at a switchboard, how would you join the protective earths?

A

Double screw connectors or soldering.