Other than a hot water system, which equipment should have an equipotential bond?
Any metallic parts of equipment that house or otherwise may come into contact with exposed live parts or conductors.
What is the minimum size MEN link when the consumer mains are not protected? What AS 3000 clause?
Rated for at least the current carrying capacity of the main neutral conductor. 5.3.5.2
Show / Name parts of earthing in the capstone electrical installation.
1 - Earth electrode
2 - Main earth conductor
3 - Main earth bar
4 - MEN link
5 - Protective earth conductors
6 - Equipotential bonds
How far from the floor are you permitted to install a main switch? Which AS 3000 clause?
2m.
2.3.3.3
Is it permissible to switch or isolate an earthing conductor? Which AS 3000 clause?
No.
2.3.2.1(c)
Is it required to identify the neutrals of circuits in a switchboard? Which AS 3000 clause?
Yes.
2.9.5.4
Is it permissible to connect a 2.5mm neutral to the load side of an RCD?
Yes, if it’s the only neutral conductor in the RCD.
What is the minimum required conductor size for an underground single phase consumer mains, in WA?
10mm.
Describe the connection and purpose of the MEN link.
Connect the main neutral and main earth at the (main) switchboard. Allows the main neutral to carry any active to earth fault current.
In a domestic switchboard, are all circuit protection devices required to operate in the same direction?
Yes.
If no earth link exists at a switchboard, how would you join the protective earths?
Double screw connectors or soldering.