HVAC Flashcards
What are the five parts of the HVAC system?
motors, ducts, fans, controls, and heat exchange units
Purpose of the HVAC system is to add or remove __ and __ to order to maintain the desired environmental conditions
heat and moisture
Summer
Cooling system is used to remove heat from air
this is usually accompanied by removing moisture
sources of cooling: Chiller, packaged unit or heat pump
Winter
heating system is used to add heat to the air
this is usually accompanied by adding moisture
sources of heat; gas fired heater, boiler or heat pump
Most cooling equipment uses a vapor compression cycle and phase changes to transfer heat
chillers, package units, split-units, fridges, freezers, etc.
Vapor Compression Cycle
What are the four main components of the vapor compression cycle?
Compressor, condenser, expansion valve, evaporator
Vapor Compression cycle __ the pressure and the temperature of refrigerant as it goes around the cycle
raises
A ton is a measure of power
One ton of air conditioning = 12,000 Btu/hr
A ton-hour is a measure of energy
One ton-hour of air conditioning = 12,000 Btu
12,000 Btu/hour is the power needed to melt __ __ of ice
one tone
Applies to both heating and cooling
= Energy moved
Energy input
= Power heat flow
Power input
The most important parameter to be measured
As the temperature changes, so does this
Coefficient of Performance (COP) =
Cooling equipment performance = Btu/hr of output / W of electric input = COP * 3.412Btu/ Wh = EER / 3.412 Btu Wh
EER
kWin/ ton = 12/ EER = 3.517/COP
Coefficients for determining equipment performance
predicts chiller efficiency at the Air Conditioning Refrigeration Institute’s (ARI) Standard Rating Point.
(AHU) and (FCU)
Integrated Part Load Value
A typical __ system sends __ water through a tall building to transfer cooling and then the air handler changes water to air to cool each space
chiller
__ __ works to evaporate water into the atmosphere
Each pound of liquid evaporated will send 1,000 Btu of heat to the atmosphere
Cooling Towers
Uses heat instead of electric power to drive a refrigeration cycle
can use waste heat but high maintenance
Absorption Chiller
Oil free variable speed compressor that can be installed as a retrofit to an existing chiller
magnetic bearing centrifugal chillers
Chilled/ hot water is circulated in the coil of the AHU, where a fan blows air to the duct system
allows control of the mix of fresh air and return air
ducted distribution systems
supplies at the same volume and temperature to the entire zone.
single zone systems
can be at different different temperatures OR flow rates
air is mixed and conditions within the machanical room adn then ducted to each zone
not used today
multizone systems
supplies both hot and cold air in separate ducts which are blended at the point of use to provide required conditions
inefficient and expensive
Dual duct systems
air is cooled to the lowest required temperature
temp is controlled by reheat coil
temperature is controlled by controlling the volume of air that is discharged into the space
energy efficient and widely used today
VAV system variable air