FIREPLACE TEST Flashcards
The open circuit reading on a thermopile is?
650-750 mv
The open circuit reading on a thermocouple is?
20-30 mv
The closed circuit on a thermopile is? (holding safety)
450-550 mv
The closed circuit on a thermocouple is?
10-15 mv
The drop out reading on a thermopile is?
40-60 mv
The drop out reading on a thermocouple is?
2-4 mv
The maximum time for the pilot stat to close after pilot outage on a thermopile is?
90 seconds
The maximum time for the pilot stat to close after pilot outage on a thermocouple is?
90 seconds
The maximum time for the pilot stat to close after pilot outage on a fireplace with a thermocouple and thermopile is?
30 seconds
The maximum volt drop across a limit switch is?
5 mv
The closed circuit on a thermocouple should not be less than?
10 mv
The reading on a thermocouple are (pilot would stay on)
Open circuit test 20 mv
Closed circuit test 13 mv
Drop out test 10 mv
Replace thermocouple
Replace the pilot stat -
Replace the pilot burner
Replace the high limit control
The reading on a thermocouple are (pilot not staying lit)
Open circuit test 15 mv
Closed circuit test 10 mv
Drop out test 4 mv
Replace thermocouple -
Replace the pilot stat
Replace the pilot burner
Replace the high limit control
The reading for a thermopile are (pilot going out)
Open circuit test 500 mv
Closed circuit test 400 mv
Drop out test 60 mv
Replace thermopile -
Replace the pilot stat
Replace the pilot burner
Replace the high limit control
If you have a fireplace with a thermopile and a thermocouple which is the flame sensor?
Thermopile
Thermocouple -