Book 100, these types of pumps are used to maintain a uniform, relatively high pressure on the fire protection system.
Pressure Maintenance Pumps
A jockey pump should be sized to make up the allowable leakage rate within ___ minutes or ____ gpm which ever is larger.
10 minutes / 1 gpm
Jockey pump should be set to operate at a pressure of ___ psi higher than the main pumps starting pressure.
5 to 10
The run-out timer is normally set for 7 to 10 minutes for electric driven fire pumps and ____ minutes for diesel driven pumps.
30 minutes
Fire pump controllers shall perform not less than ____ automatic and ___ manual operations during the Acceptance test and shall be operated for a period of least 5 minutes at full speed during each of the test.
10 / 10
Tamper switches are placed on valves in firefighting water systems of buildings to prevent unauthorized closing, The switch will activate within ___ turn when the valve is operated from full open towards the closed position.
2
The batteries are connected in ___ to the rest of the electrical system.
Parallel
The six battery system, ___ of the 6 batteries are used to start the apparatus.
5
When the apparatus is out of service for an extended period of time ( over ____ hours or the on-board battery charger cannot be plugged in) the radio “cut off switch” must be turned off to avoid running down the battery.
10 hours
The Assignment Record is
F702
The Repair Record is
F705
The Statistical Information Record is
F701
The Maintenance Record is
F704
The Inventory Record is
F709
The Battery Record is
F706
The Tire Record is
F710
The Yearly Mileage Report is
F380
The Hydrant Report is
F376
The Hydrant Record is
F95
The Hydrant Test Record is
F70