electricity second half Flashcards
They automatically open circuit if unsafe current is detected.
electric protective devices
Fuses
melt
breakers
flip
GFCIs
Isolate the load
GFCI cuts electricity off __ of a second if a ground fault is detected.
1/40th
GFCI’S should be used on all _____, or have an assured equipment grounding conductor program.
120-volt, single phase, 15-20 ampere receptacles
Tripping GFCI’s are designed to trip at____.
4-6 milliamps
GFCI’s are not required on permanent power ________.
unless tool used with extension cord
GFCI’S or ____ are required for all temporary power during construcution.
assured equipment grounding conductor program
If a GFCI detects as imbalance as small as ___ it reacts as fast as ___ of a second.
- 5 milliamps
2. 1/30th of a second
GFCI is useless if ground prong is____.
missing
GFCI required on generators ____ or greater.
5 kW or 5,000 watts
GFCI can be built in or added as a ____.
pig tail
All cord sets, recptacles and any equipment connected by cord shall be ______.
Inspected before each days use
Must be kept onsite.
Written program
What is covered by assured grounding?
electric tools/power tools. Cords, plugs, receptacles not part of the building.
Assured Grounding test records are kept by_____.
color coding, other means, written log.
electrical equipment must be inspected____.
before insulation and to make sure it is suitable for it’s intended use.