EDG Mechnaical Flashcards

1
Q

Discuss EDG air compressors rating and tech spec value

A

Air start receivers are capable of 5 starts together or 2 solo.
Tech spec value 310#
Back-up compressor is only for Control air not starting air
Main Air compressor is deenergized by HR9 Relay of EPS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

Discuss EDG local remote switch on auto start signals

A

In REMOTE EDG will start as normal
In LOCAL only LOP will start Diesel, BKR will not auto close
In MAINTENACE EDG will not auto start

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

Discuss EDG HSR

A

HSR: engine speed> 375 RPM or Coolant pressure >375 RPM equivalent

  • DAH fans start
  • Starting air cutout
  • Back up Field flash (normal start only flash, E-start 2nd try)
  • Jacket HTR and Keep warm pumps are off
  • Arm alarm and shutdown Circuits after 7 second delay
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

Discuss EDG LO-LO Speed Relay

A

LSR: 95 RPM

Air shut off, starting air is no longer admitted to EDG

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

Discuss EDG LSR

A

LSR: 125 RPM

  • Drops out start circuit relays
  • Opens SW to DG HX
  • Starts Crankcase Exhauster
  • Flashes Field (e-start)
  • De-energizes Generator space heater
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

Tech Specs for Fuel oil and capacities

A

FOST: 75,000 capacity 62,000 TS Limit (60,000 modes 5/6)
FODT: 1,500 capacity 600 TS Limit

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

Motor driven and aux lube oil pump auto start

A

HSR energized and 1 of 2
OPL1 (70#) or OPL2 (65#)
Stays running once started

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

Motor driven Aux coolant pump auto start

A

HSR energized and

<25# Jacket or <24.5# Air Cooling loop

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

List EDG Trips

A

Engine over Speed - 110 to 112%
2/3 low lube oil pressure OPL-2,3,4 (65#, 60#, 60#)
Generator Differential (86DP)
Emergency Stop
Hi Lube oil temp 173F (note 1 and 2)
Hi Jacket Coolant temp 195F (note 1 and 2)
Generator Backup Protection (86DB) (Note 1)
Note 1: Trips bypassed on SI via RLA relay
Note 2: Trips bypassed on E-start

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

List MCB status light indication for EDG

A
EDG Not Available
EDG Parallel Operations
EDG Back up protection Bypassed (SI)
EDG Local Control
EDG Emergency start (LOP/SI/E-start)
EDG EDG Maintenance
EDG High Temp Bypassed (any E-start)
EDG Regulator in manual
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

State when EDG governor swaps between isochronous and Droop

A

If EDG is paralleled then it will be in DROOP

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

What happens when EDG gets a shutdown Signal

A

The Shutdown Solenoid is energized, this sends air to opposite side of the rack boost cylinder

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

Motor Driven Fuel Oil pump start signal

A

15# at outlet of filter and speed>HSR

Stays running until EDG is shutdown

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

Discuss EDG LO heatexchanger

A

3-way control valve Maintains temperature between 125F and 142F

How well did you know this?
1
Not at all
2
3
4
5
Perfectly