EDG Mechnaical Flashcards
Discuss EDG air compressors rating and tech spec value
Air start receivers are capable of 5 starts together or 2 solo.
Tech spec value 310#
Back-up compressor is only for Control air not starting air
Main Air compressor is deenergized by HR9 Relay of EPS
Discuss EDG local remote switch on auto start signals
In REMOTE EDG will start as normal
In LOCAL only LOP will start Diesel, BKR will not auto close
In MAINTENACE EDG will not auto start
Discuss EDG HSR
HSR: engine speed> 375 RPM or Coolant pressure >375 RPM equivalent
- DAH fans start
- Starting air cutout
- Back up Field flash (normal start only flash, E-start 2nd try)
- Jacket HTR and Keep warm pumps are off
- Arm alarm and shutdown Circuits after 7 second delay
Discuss EDG LO-LO Speed Relay
LSR: 95 RPM
Air shut off, starting air is no longer admitted to EDG
Discuss EDG LSR
LSR: 125 RPM
- Drops out start circuit relays
- Opens SW to DG HX
- Starts Crankcase Exhauster
- Flashes Field (e-start)
- De-energizes Generator space heater
Tech Specs for Fuel oil and capacities
FOST: 75,000 capacity 62,000 TS Limit (60,000 modes 5/6)
FODT: 1,500 capacity 600 TS Limit
Motor driven and aux lube oil pump auto start
HSR energized and 1 of 2
OPL1 (70#) or OPL2 (65#)
Stays running once started
Motor driven Aux coolant pump auto start
HSR energized and
<25# Jacket or <24.5# Air Cooling loop
List EDG Trips
Engine over Speed - 110 to 112%
2/3 low lube oil pressure OPL-2,3,4 (65#, 60#, 60#)
Generator Differential (86DP)
Emergency Stop
Hi Lube oil temp 173F (note 1 and 2)
Hi Jacket Coolant temp 195F (note 1 and 2)
Generator Backup Protection (86DB) (Note 1)
Note 1: Trips bypassed on SI via RLA relay
Note 2: Trips bypassed on E-start
List MCB status light indication for EDG
EDG Not Available EDG Parallel Operations EDG Back up protection Bypassed (SI) EDG Local Control EDG Emergency start (LOP/SI/E-start) EDG EDG Maintenance EDG High Temp Bypassed (any E-start) EDG Regulator in manual
State when EDG governor swaps between isochronous and Droop
If EDG is paralleled then it will be in DROOP
What happens when EDG gets a shutdown Signal
The Shutdown Solenoid is energized, this sends air to opposite side of the rack boost cylinder
Motor Driven Fuel Oil pump start signal
15# at outlet of filter and speed>HSR
Stays running until EDG is shutdown
Discuss EDG LO heatexchanger
3-way control valve Maintains temperature between 125F and 142F