4160V Flashcards

1
Q

State what 13.8 bus duct fault causes

A

Opens:

  • Associated 345kV Breakers
  • MGB for UAT bus duct fault
  • 13.8 kV incoming Line breaker
  • 4160 V incoming line breaker
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

List causes of UAT incoming Supply Breaker trip

A
UAT/ Bus duct faults
345 bus 6/ 25kV Isophase bus fault
Switchgear enclosure fault
Breaker failure (11,12, MGB)
GSU fault
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

List causes of RAT incoming Supply Breaker trip

A

RAT/ bus duct faults
345 kV Bus 5 fault
Switchgear enclosure fault
Breaker failure (345 kV 52, 695)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

List bus 3 and 4 UV auto actions

A

Trips large loads (94 relays)
-CO pumps first
-HD pumps next
Block RAT auto-transfer

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

List bus 3 and 4 RAT Breaker Auto-Transfer

A
Sync exits or
existed within the last 1 second
Bus Voltage <17% and
UAT breaker begins to open - remote only
Available for 2.0 sec
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

List Bus 5 and 6 Breaker Auto-transfer

A
Sync exits or
existed within the last 1 second
Bus Voltage <25% and
UAT breaker begins to open - remote only
Available for 1.2 sec
How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

List first and second level undervoltage

A

1st level:
- <70% voltage for > 1.2 seconds with RAT available
- <70% voltage w/o RAT
2nd level
- <95% rated voltage with an SI signal for >6 seconds

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

List Bus 5 and 6 UV Auto actions

A

Trips large loads (94 relays)
Block RAT auto-transfer
UAT and RAT blocked open by RMO for Diesel to power bus

How well did you know this?
1
Not at all
2
3
4
5
Perfectly