480V Flashcards
Discuss 4 methods of electrical fault protection for Containment penetraitions
2 motor starters in series for motors <5HP
1 thermal magnetic breaker with 1 motor starter for motors>5HP
2 thermal magnetic circuit breakers in series
T.S. 3.8.4.1 Locked breakers
Discuss actions required to reclose Breaker that has tripped from 86 relay
condition must be clear (ground fault/ overcurrent)
86 device locally reset
Discuss operation of 480V ground detection
3 Volt meters, 1 per phase
grounded phase decreases potential across transformer, indication decreases
other phases indication increases
List 125VDC use in a US
Control power
Breaker position indication
relay power
what Load Center is powered from 4160
Load center 3 for FPH
List power supplies for SWYD ABT
Normal: US:14/26
Emergency: US-53
Normal power seeking
List loads of SWYD ABTs
Battery chargers
345kV breaker auxiliaries
120/240V distribution panels
Discuss indications in SWYD ABTs
2 white lights- power available
Green light - powered from normal source
Red light - powered from emergency source
2 amber lights - supply breakers trip on overload
List setpoints for US fan
Fan start: 375F
Alarm: 410F
Discuss T.S. 3.8.3.2
Immediately suspend core alterations statement for degraded electrical (Modes 5/6)
Discuss T.S. 3.8.4.1
Breakers but be tripped open in found closed (modes 1,2,3) with in 1 hour unless controlled by procedure for up to 72 hours