13.8 KV Flashcards
Describe how the 13.8KV distribution system is protected from damage resulting from full phase to ground faults
a. A grounding resistor rated for 600A for 10 seconds has been installed to allow the ground fault relays to function before the ground damages the transformer
State the function of the UAT pressure-vacuum bleeder valve and describe operation
a. Designed to accommodate season and operational changes in temperature/gas space pressure, opens to relieve pressure
Draw and label 13.8KV one-line
see drawing PDF
State the function of the UAT/RAT tap chargers
a. Allows no-load charging of the transformer primary to secondary voltage ratio without having to break the transformer seal.
Describe how the UATs and RATs are cooled, including flow-paths and auto-control features
a. UATs: 8 oil-to-air heat exchangers with isolation valves and 4 fans, auto on at 70C and off at 65C, powered from MCC 131/261
b. RATS: 12 fans with 4 HXs auto on at 70C of <70C, powered from 131/261
Describe the three general types of fault detection (including sensing devices and parameters sensed) common to both the UATs and the RATs
a. UAT Primary Protection (86UP)
i. Differential Current only (87UP) – senses current flow imbalance from UAT supply to isophase bus ducts to swgr sides of the 13.8/4.16kv busses.
b. UAT Backup Protection (86UB)
i. Timed OverCurrent (51)
ii. Ground Fault (51N) – 600 amps for 10 seconds. Uses single current transformer on grounding resistor of transformers 13.8kv secondary winding. If current flow to grounding resistor exceeds setpoint for GFR, the relay is actuated.
iii. Sudden Pressure Relay (63FPX) – 2 of 3 logic
1. Used to detect excessive rate of oil pressure increase within the transformer, as a result of internal arcing.
2. An internal transformer fault that causes arcing vaporizes the insulating oil, resulting in a rapid pressure increase.
3. Gradual temperature changes will not result in actuation.
c. Overcurrent (51) – specific to UAT only. Uses current transformers of each phase of 25kv-segregated bus to monitor current flow. If current exceeds setpoint, relay is actuated.
Describe how and electrical fault within the UAT and RAT will affect the station electrical distribution system
a. UAT: Trips Turbine, Opens MGB, Opens Exciter Field Breaker, Isolates Buses 1-6 UAT supply breakers, Opens SY PCB 11 and 12, Isolates UAT cooling Auxiliaries
b. RAT: Trips open Buses 1-6 RAT supply breakers, Opens 345 KV PCBs 52 and 695, isolates RAT cooling fans
Describe how the gas mixture in the UAT gas space is maintained inert
The air space above the oil is charged with nitrogen
State the function of the UAT/RAT mechanical pressure relief device and describe its operation
a. UAT: Relieves excess tank pressure, opens at 11.5#, seats are 8#
b. RAT: Relieves excess tank pressure, opens at 10#, seats at 5#
Describe the UAT/RAT fire protection Schemes
AT 190F foam insulation is melted and two wires come into contract activating the detection circuit which opens the associated deluge valve
Describe the operation the RAT oil preservation system
0.5# overpressure is maintained on oil
Describe the routing of the 13.8KV bus ducts from the UAT/RATs to the 13.8KV buses
From UATS/RATS in non-segregated bus ducts through the TB to SWGR
Describe the motive power for operation of the 13.8KV incoming supply breakers and load feeder breakers
Closing springs charged via motor powered from 125VDC (control power)
Describe all the uses for 125VDC power within a 13.8KV breaker enclosure, including the impact of losing DC control power
a. Closing springs charging motor
b. Undervoltage protective relaying
c. Breaker control power
State the function of the 13.8KV breaker closing spring charging motor
Compresses the closing springs until fully charged, the springs discharge and close the breaker