345 KV Flashcards
List normal/tripping pressures for low SF6 pressures in bus zones
MEPPI: 57/43#
low pressure causes bus segment isolation
List normal/tripping pressure for low pressure SF6 breakers
ITE: 45/30-34#
MEPPI: 86-71#
Trips and Locks out breaker
List normal/tripping pressures for high pressure SF6
ITE: 265/230#
Trips and locks out breaker
State opening/closing mechanism for SWYD breakers
ITE: Spring Open/ Air close
MEPPI: Spring operated
State air system pressure Normal/Lockout
250/225#
Locks out closing
State interlock for SWYD breakers 11 and 12
Dispatch can neither open the last breaker nor close the first breaker
State locations that SWYD MODs can be operated from
Relay room
Locally
MCB
ECSS (not T-5006 or G-106)
State locations that 345kV breakers can be operated from
Relay room
Locally
MCB
ECSS
Discuss MCB light indication for SWYD breakers
Red/Green => position (closed/open)
MCB: Red when all three poles closed
MANCHESTER: one pole closed will receive red light (covers safety protection of any phase energized)
Blue => Remote control available
Both MCB or ESCC
Relay room switch is in the remote position
Discuss relay room light indication for 345 SWYD breakers
Two Red lights – One for each set of trip coils (Sys #1 & Sys #2)
Means that all 3 poles of the PCB are shut and the 3 trip coils have continuity
One Green light
Means that the all 3 poles of the PCB are open.
State T.S. 3.8.1.1 action statement
Perform Surveillance Requirement 4.8.1.1.1.a for the OPERABLE offsite
circuit within 1 hour and at least once per 8 hours thereafter
State T.S. 3.8.1.2 requirements
With less than the above minimum required A.C. electrical power sources OPERABLE,
immediately suspend all operations involving CORE ALTERATIONS, positive reactivity
changes, movement of irradiated fuel, or crane operation with loads over the fuel
storage pool, and within 8 hours, depressurize and vent the Reactor Coolant System
through a greater than or equal to 1.58-square-inch vent