345 KV Flashcards

1
Q

List normal/tripping pressures for low SF6 pressures in bus zones

A

MEPPI: 57/43#

low pressure causes bus segment isolation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

List normal/tripping pressure for low pressure SF6 breakers

A

ITE: 45/30-34#
MEPPI: 86-71#
Trips and Locks out breaker

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

List normal/tripping pressures for high pressure SF6

A

ITE: 265/230#

Trips and locks out breaker

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

State opening/closing mechanism for SWYD breakers

A

ITE: Spring Open/ Air close
MEPPI: Spring operated

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

State air system pressure Normal/Lockout

A

250/225#

Locks out closing

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

State interlock for SWYD breakers 11 and 12

A

Dispatch can neither open the last breaker nor close the first breaker

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

State locations that SWYD MODs can be operated from

A

Relay room
Locally
MCB
ECSS (not T-5006 or G-106)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

State locations that 345kV breakers can be operated from

A

Relay room
Locally
MCB
ECSS

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

Discuss MCB light indication for SWYD breakers

A

Red/Green => position (closed/open)
MCB: Red when all three poles closed
MANCHESTER: one pole closed will receive red light (covers safety protection of any phase energized)
Blue => Remote control available
Both MCB or ESCC
Relay room switch is in the remote position

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

Discuss relay room light indication for 345 SWYD breakers

A

Two Red lights – One for each set of trip coils (Sys #1 & Sys #2)
Means that all 3 poles of the PCB are shut and the 3 trip coils have continuity
One Green light
Means that the all 3 poles of the PCB are open.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

State T.S. 3.8.1.1 action statement

A

Perform Surveillance Requirement 4.8.1.1.1.a for the OPERABLE offsite
circuit within 1 hour and at least once per 8 hours thereafter

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

State T.S. 3.8.1.2 requirements

A

With less than the above minimum required A.C. electrical power sources OPERABLE,
immediately suspend all operations involving CORE ALTERATIONS, positive reactivity
changes, movement of irradiated fuel, or crane operation with loads over the fuel
storage pool, and within 8 hours, depressurize and vent the Reactor Coolant System
through a greater than or equal to 1.58-square-inch vent