E51 - RCIC Flashcards

1
Q

When will the min flow valve auto open? and when will it auto close?

A

> 125 psig AND < 95 gpm OPEN

> 175 gpm CLOSED

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
2
Q

What are the RCIC turbine throttle trips? (trips the trip/throttle valve)

A

SOMIE

Suction pressure low > or equal to 6.5”hg (electrical)

Overspeed – approximately 5520 RPM (120%) (mechanical)

Manual PB (Electrical)

Isolation (group 4 isolation) Div 1 OR div 2 signal (Electrical)

Exhaust pressure high (turbine exhaust) > or equal to 25 psig (Electrical)

and also the local trip lever (mechanical)

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
3
Q

What pump will swap to suppression pool on high level first, RCIC or HPCS?

A

RCIC

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
4
Q

How does the Gland Seal Compressor respond to a LOCA?

A

Trips on Div 1 ECCS initiation,
When signal resets, compressor will auto restart
If level is < -41.6”, AND RCIC gland seal compressor H/S has been taken to stop.

If level is >-41.6” it should manually be started if RCIC is running

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
5
Q

When will the RCIC steam line warmup valve F076 close?

A

Group 4 isolation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
6
Q

When does the F063 and F064 Steam Supply inboard and outboard isolation valves auto close?

A

Group 4 isolation

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
7
Q

When does the RCIC Steam supply drain trap bypass auto open?

A

Steam supply drain pot level is high

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
8
Q

What is the normal position of all drain valves?

A

open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
9
Q

when will the drain valves change position?

A

Closes when the F045 is Not Full closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
10
Q

when can the drain valves be opened?

A

Can only be opened if F045 is full closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
11
Q

how do drain valves fail on loss of power?

A

Fail closed

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
12
Q

Can the gland seal compressors be secured if an actual initiation signal is present?

A

NO

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
13
Q

What light indication is available from the P150 panel of the trip/throttle valve?

A

Motor position only! not actual valve position.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
14
Q

What flow does the Min/flow restrict flow to? and where does it discharge to?

A

90 gpm to the suppression pool

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
15
Q

where does RCIC Turbine Exhaust to?

A

Suppression Pool

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
16
Q

What is the logic for closing RCIC inj valve on level 8?

A

B and A at +53.5”

Closes F045, which closes F013 injection valve.

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
17
Q

How does the F077, F078, and F068 respond to a group 9 isolation?

When can they be reopened?

A

Close on group 9

77 and 78 require BOTH signals clear
F068 only requires one signal to be clear

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
18
Q

How do you reset a RCIC trip?

A

Take trip throttle valve closed and then back open

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
19
Q

What is the indication of an electrical trip? TTV

A

After reset, one green light and one red light

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
20
Q

what is the indication of a mechanical trip? TTV

A

Both lights are green

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
21
Q

What is indication that all trips are clear, TTV

A

both lights red

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
22
Q

What signals initiate RCIC?

A

Arm and depress manual P/B OR

-41.6” wide range

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
23
Q

When does RCIC isolate?

A

+53.5” Rx Level Narrow Range

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
24
Q

Where does RCIC inject into the RX?

A

“B” Feedwater line

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
25
Q

Where does RCIC steam come from?

A

“A” main steam line, upstream of the MSIV

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
26
Q

What RPM should RCIC turbine stay above?

why?

A

> 2,000 rpm

at <2,000 rpm, pump is not able to:

1) provide adequate oil pressure for turbine bearing lubrication and for governor actuator control oil.
2) chattering of the turbine exhaust check valve

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
27
Q

Where does RCIC get its primary and backup suction from?

A

CST, backup is suppression pool

How well did you know this?
1
Not at all
2
3
4
5
Perfectly
28
Q

how many gallons in CST are reserved for RCIC and HPCS?

and what else can CST do?

A

170,000 gallons

Return path for testing purposes

29
Q

what is the supervisor showing?

A

stem position

30
Q

what is the trip throttle valve light showing

A

motor position

31
Q

what is the purpose of the turbine exhaust vacuum breakers?

A

prevent drawing a vacuum in RCIC turbine exhaust line following RCIC operation

32
Q

purpose of the gland seal compressor?

A

provides compressed air to turbine glands to prevent steam leak into RCIC room

33
Q

purpose of the lube oil system?

A

supplies lubricant for turbine bearings and makeup oil for hydraulic mechanical actuator of the RCIC turbine governor system

34
Q

purpose of the governor?

A

limits turbine speed to maximum valves and positions governor valve to maintain constant pump discharge flow over the full pressure range of operation

35
Q

what should be done if RCIC injection in mode 1?

A

Enter loss of Feedwater heating ONEP

36
Q

How long must test switch remain in test after valve stroke is complete?

A

30 seconds

37
Q

when will the manual isolation pushbutton work?

A

only after manual or automatic initiation is sealed in

38
Q

what happens on initiation sequence?

A

immediately:
Open signals to F095, F010, F046
Close signals to F022, F029 (CST return valves)
Start signal to gland seal compressor. Div 1 manual isolation logic enable

After 6 second TD:
open signals to F045, F013
F095 Closes on F045 Full open

39
Q

what pressure can RCIC inject into the RX?

A

165 to 1192 psia

40
Q

what’s the purpose of the turbine exhaust rupture disk?

A

protects the turbine casing and exhaust piping from overpressurization due to exhaust blockage

41
Q

When will the RCIC vacuum breakers auto close?

A

Group 9

42
Q

What closes on a turbine trip?

A

Trip throttle valve

43
Q

How do you reset a turbine trip?

A

Take TTV closed, then open.

check lights to see what type of trip it is

44
Q

What is the normal position of F068, RCIC turbine exhaust to suppression pool?

A

Open

45
Q

When will F068, RCIC turbine exhaust to suppression pool, auto close?

When can it be reopened?

What will NOT occur if F068 closed?

A

< 60 psig Rx AND 1.39 psig drywell pressure (group 9)

Can be reopened if EITHER of the above signals clear

If F068 is closed, The F095 or F045 will NOT open

46
Q

When will the Test return to CST auto close? (Inboard and outboard)

A

if F031 full open (suppression pool suction)

47
Q

what are the AC valves for RCIC with Power Supplies?

A
63  16B31
64  15
76  16
77  15
78  16
48
Q

What cools RCIC room ventilation system?

A

SSW A

49
Q

How do Air operated valves fail for RCIC?

A

Closed, It also results in a loss of test return line back to CST

50
Q

When does the CST Suction F010 get open signal?

A

Auto open on initiation IF F031 is NOT full open (Supp pool suction)

51
Q

When will CST Suction F010 auto close?

A

Auto closes if F031 full open (Supp pool suction)

52
Q

When can the CST Suction F010 be opened or closed?

A

Any time from either panel, BUT when travel complete, it will reposition if demand signal is present.

53
Q

When will F031, Supp pool suction valve AUTO OPEN?

A

<4’ CST or >18’9” suppression pool

54
Q

When will F031, Supp pool suction valve AUTO close?

A

Group 4 isolation

55
Q

What rpm does RCIC turbine trip?

A

5520

56
Q

what is the power supply to the gland seal compressor?

A

1DA2

57
Q

power supply to the RCIC Turbine Supply Governor Control?

A

11DA

58
Q

How does the Governor fail on loss of power?

A

Open, which causes an overspeed trip so you can reset trip and run RCIC turbine by manually throttling trip throttle valve

59
Q

When will RCIC swap from CST to supp pool suction?

A

<4’ CST or >18’9” Suppression pool

60
Q

What happens if the F045 doesn’t open? and what speed will RCIC be at?

A

Ramp Generator won’t start
Governor will be OPEN
Speed will be around 2,000 rpm

61
Q

Is the RCIC Governor normally closed or normally open?

A

Open

62
Q

When will the RCIC Governor throttle?

A

Throttles on F045 coming open

63
Q

When will the steam supply F045 Auto open?

A

on initiation IF F068 full open AND <53.5” Rx level

64
Q

When will steam supply F045 Auto close?

A

> 53.5”

65
Q

Where can F045 be opened from with >53.5” Rx Level?

A

P150 (no interlocks)

66
Q

Where can F045 be opened from with F068 (RCIC turbine exhaust to Supp pool) open?

A

Nowhere!! ???? Should it say the 68 closed..?

67
Q

What is the normal RCIC Test Return FCV to CST position?

A

Position 2

68
Q

When will the Inj Valve F013 Auto open?

A

Initiation signal if F045 AND TTV not full closed

69
Q

when will the inj valve F013 Auto close?

A

Auto close if TTV or F045 Full closed